Analog Output Calibration

Analog Output Calibration is an application embedded within the DD file that allows for remote configuration of the analog

output Navigate to Configuration > M2000 > Advanced > Analog Output and select D/A Trim Follow the on-screen instructions

for further details

Do not exercise the D/A Trim application if meter is configured in multi-drop mode The output current is fixed in multi-drop

mode (that is, Polling address is non-zero)

This application uses the custom offsets The deviation from 4 mA and 20 mA must be entered in terms of milliamperes

Recalibration will take effect once all offsets are configured and the application has completed

Figure 6 is an example of a diagram for a setup intended to assist in calibrating the analog output

42

41

250 Ω

Load

Polling Address = 0

44

43

Reference Meter

Fluke Amp Meter

Handheld Field

Communicator

Figure 6: Setup to Assist in Calibrating Analog Output