Analog output calibration – Badger Meter M-Series M2000 User Manual
Page 15

Analog Output Calibration
Analog Output Calibration is an application embedded within the DD file that allows for remote configuration of the analog
output Navigate to Configuration > M2000 > Advanced > Analog Output and select D/A Trim Follow the on-screen instructions
for further details
Do not exercise the D/A Trim application if meter is configured in multi-drop mode The output current is fixed in multi-drop
mode (that is, Polling address is non-zero)
This application uses the custom offsets The deviation from 4 mA and 20 mA must be entered in terms of milliamperes
Recalibration will take effect once all offsets are configured and the application has completed
Figure 6 is an example of a diagram for a setup intended to assist in calibrating the analog output
42
41
250 Ω
Load
Polling Address = 0
44
43
Reference Meter
Fluke Amp Meter
Handheld Field
Communicator
Figure 6: Setup to Assist in Calibrating Analog Output
Installation & Operation Manual
Page 15
December 2012