NORD Drivesystems BU0570 User Manual

Page 24

Advertising
background image

EtherCAT bus module for NORD frequency inverters SK 5xxE

24

Subject to technical amendments

BU 0570 GB-0312

4.2.6

Beispiel für FU das Ein- / Ausschalten des Frequenzumrichters

In this example, a FI will be operated with a setpoint (setpoint frequency) and an actual value (actual
frequency). The "Maximum Frequency" is 50Hz.

Parameter settings:

 P105 = 500
 P543 = 1
 P546 = 1

Control
word

Setpoint 1

Status word

Actual

value 1

Explanation

- - -

- - -

0000h

0000h

- - -

- - -

xx40h

0000h

The mains voltage is switched on at the FI

047Eh

0000h

xx31h

0000h

FI is set to "Standby" status

047Fh

2000h xx37h 2000h

FI is set to "Operation enabled" status and controlled with a
50% setpoint.

The FI is enabled, the motor is supplied with current and rotates with a frequency of 25Hz.

0047Eh

2000h xx31h 0000h

FI is set to "Standby" status, the motor runs up its
parameterised ramp to speed 0 and is switched off.

The FI is disabled again and the motor is without current.

047Fh

1000h xx37h 1000h

FI is set to "Operation enabled" status and controlled with a
25% setpoint.

The FI is enabled, the motor is supplied with current and rotates with a frequency of 12.5Hz.

Table 17 Example of setpoint specification

4.2.7

Timeout monitoring

Data traffic on the EtherCAT side is monitored by EtherCAT watchdogs. Monitoring via the FI parameter
P513 is also possible.
P513 monitoring is triggered if the process data contact is interrupted or the process data is transferred with
an invalid control word (Bit10 in control word = 0). This function is activated when the first valid process data
telegram is received.

Advertising