EtherCAT bus module for NORD frequency inverters SK 5xxE

36

Subject to technical amendments

BU 0570 GB-0312

Parameter

Setting value / Description / Note

Device

Parameter
type

P745

Option version

(Module version)

SK 5xxE

0.0 ... 999.9

Version status (software version) of the technology unit (SK TU3-xxx), but only when own
processor is present, therefore not for SK TU3-CTR.

Have this data available if you have a technical query.

P746

Option status

(Module status)

SK 5xxE

S

0000 ... FFFF (hex)

Actual status (readiness, error, communication) of the technology unit (SK TU3-xxx), but only
when own processor is present, therefore not for SK TU3-CTR.

Possible values:

Bit 0

= EtherCAT state "Pre- Operational"

Bit 1

= EtherCAT state "Save- Operational" or "Operational"

Bit 2

=

Vacant

Bit 3

=

Vacant

Bit 4

= Error 1

Bit 5

= Error 2

Bit 6

= Error 3

Bit 7

=

Vacant

Bit 8 – Bit 15 = Module number (EtherCAT = 20)

Error table

Error 3 | Error 2 | Error 1 |

Meaning

0 0 0

No error

0 0 1

EtherCAT ASIC cannot be accessed

0 1 0

EtherCAT watchdog timeout

0 1 1

P513 timeout

1 0 0

General EtherCAT configuration error

NOTE

When activated, the functions block current, quick stop, remote control and cancel error
are available at the (local) control terminals. To operate the drive, a high signal must be
present on the digital inputs being used before the drive can be enabled.