NORD Drivesystems BU0570 User Manual

Page 28

Advertising
background image

EtherCAT bus module for NORD frequency inverters SK 5xxE

28

Subject to technical amendments

BU 0570 GB-0312

5 Parameter

5.1 Parameterisation of the EtherCAT module SK TU3-ECT

The following parameters affect the bus modules.

5.1.1

EtherCAT parameters

These parameters are from the EtherCAT standard and are supported by the SK TU3-ECT.

Parameter

[Sub Index]

Access

Type

Setting value / Description / Note

0x1000
[0]

read only

32Bit Device type and functionality

0x1008
[0]

read only String Designation of module

0x1009
[0]

read only String Hardware version

0x100A
[0]

read only String Software Version

0x1018
[0] = 4
[1] = Vendor ID
[2] = Product code
[3] = Revision
[4] = Serial Number

read only

32Bit Information for the module "Serial Number" is not supported.

0x1600
[0] – [4]

read only

32Bit Mapping for the setpoint PDOs

0x1A00
[0] – [4]

read only

32Bit Mapping for the actual value PDOs

0x1C00
[0] – [4]

read only

8Bit

Assignment and use of Sync channels

0x1C12
[0] – [1]

read only

16Bit Process data output

0x1C13
[0] – [1]

read only

16Bit Process data output

Table 19 EtherCAT parameters

5.1.2

BUS module standard parameters (P15x)

Access:

Read/Write

Parameter

{Factory setting}

Setting value / Description / Note

Device

Parameter
type

P152

Factory setting

(Factory setting)

SK TU3-ECT

16 bit

0 ...1

{ 0 }

By selecting the appropriate value and confirming it with the ENTER key, the selected
parameter range is entered in the factory setting. Once the setting has been made, the value of
the parameter returns automatically to 0.

0 = No change:

Does not change the parameterisation.

1 = Load factory settings:

The complete parameterisation of the FI is reset to the factory

setting. All originally parameterised data are lost.

Advertising