EtherCAT bus module for NORD frequency inverters SK 5xxE

30

Subject to technical amendments

BU 0570 GB-0312

Parameter

Setting value / Description / Note

Device

Parameter
type

P176

[-01]


[-27]

PZD bus IN

(Process data bus IN)

SK TU3-ECT

16 bit

Allocation of process data which have been received (data sent from PROFINET IO controller).

-32768 ... 32767

[-01] =

Bus module outputs

[-02] =

Control word for FI1

[-03] =

Setpoint 1 for FI1

[-04] =

Setpoint 2 for FI1

[-05] =

Bus module outputs

[-06] =

Control word for FI1

[-07] =

Setpoint 1 for FI1

[-08] =

Setpoint 2 for FI1

P177

[-01]


[-27]

PZD bus OUT

(Process data bus OUT)

SK TU3-ECT

16 bit

Allocation of process data which have been transmitted (data sent to the PROFINET IO
controller).

-32768 ... 32767

[-01] =

Bus module inputs

[-02] =

Status word from FI1

[-03] =

Actual value 1 from FI1

[-04] =

Actual value 2 from FI1

[-05] =

Bus module inputs

[-06] =

Status word from FI1

[-07] =

Actual value 1 from FI1

[-08] =

Actual value 2 from FI1


5.1.4

BUS module information parameters, bus-specific (P18x)

Zugriff:

Read

only

Parameter

Setting value / Description / Note

Device

Parameter
type

P181

Second Address

(Second Address)

SK TU3-ECT

16 bit

0 ... 4095

Address set with the DIP switch.

P184

SPI error counter

(SPI error counter)

SK TU3-ECT

16 Bit

0 ... 0xFFFF

Counts transmission errors between the ASIC and the SK TU3-ECT processor. This value is set
to 1 as default.