Rack Mounting/Desktop Placement

Page 2-5

Rack Mounting/

Desktop

Placement

The IntraSwitch can be installed in most standard 19-inch
equipment racks. It can also be placed on a horizontal surface
with support capabilities of 11 pounds (5 kilograms).

Equipment Rack

Installation

To install the IntraSwitch in an equipment rack:

Important: Disconnect all cables from the
switch before continuing.

1

Place the switch on a stable, flat surface.

2

Locate a rack bracket (supplied) and place it
over the mounting holes on one side of the unit,
as shown in Figure 2-2.

Figure 2-2

Mounting rack bracket on the IntraSwitch

3

Insert the four screws (supplied) into the holes
and tighten with a Phillips screwdriver.

4

Repeat the two previous steps for the unit’s
other side.

5

Place the IntraSwitch in the equipment rack.

Important: Make sure the switch is sup-
ported until all four mounting screws for each
bracket are installed.

6

Secure with mounting screws.

The switch is ready to be connected to the network.
See “Connecting to the Network” on page 2-7.