Chapter 5: Alarms

90

©

2012 Vaisala Canada Inc

If you want to apply an existing alarm template (which

defines how the alarm displays and who is notified when a

threshold is reached), select

Use Alarm Template

(see

“Creating Alarm Templates” on page 84).

4

If you want to define custom settings for this template,

complete the fields in the General Parameters,

Notifications, and Comments tabs.This option is also

available using the right click context menu while a

template is highlighted.

5

When you are finished creating your threshold template,
click

Save

.

Threshold Alarms

Users with the correct permissions set device channel

thresholds that trigger alarms. For example:
• Greater than 23.00 C for more than 1 minute
• Less than 37.76 RH for more than 15 minutes
You can set a threshold alarm using a template (if previously

configured), or set a custom alarm.

Setting Threshold Alarms

You can configure several threshold alarms, for example, one

for yellow alarms (mild concern), another for red alarms

(extreme concern). For example, you could set a yellow

alarm to trigger first (at one minute out of threshold), and

send an email to someone who needs to know. For a red

alarm, you could set the alarm condition to a longer time

(15 minutes out of threshold) and send the email to a lab

manager, or a distribution list of people who need to be

notified to take action.