Creating Alarm Templates

viewLinc 4.1 Administrator Guide

85

You can also create a reusable threshold condition and

assign it to a specific alarm template.

To create an alarm template:

1

From

Options | System Configuration | Templates |

Alarm Templates

, click the

Options

dropdown, then

select

Add Alarm Template

.

2

By default, the alarm template name is New Alarm

Template. Click in the title to enter a more specific title.

3

On the General Parameters tab, define the following:

a

Color Code.

Choose the alarm color code - either blue,

yellow, orange, or red. This color is used as the color

indicator for alarms on the Alarms tab, and as the

background color for a row in locations, if activated. It

is also used as the color for a threshold line in a real-

time graph. Use the color codes to indicate severity,

starting with blue for less serious alarm conditions, es-

calating to red for the most serious alarm conditions.

b

Alarm Message.

If you want to set up an alarm email

notification (set up on the Notifications tab), enter the

message you want to appear in the alarm notification.

c

Delay Before Activating Alarm (HH:MM).

If desired,

specify a delay period, in hours and/or minutes, from

when a condition exists and you want the alarm trig-

gered.

d

Acknowledgement Required.

Select this option if you

require an individual to acknowledge an alarm. If you

select this option, the alarm will remain on the Alarms

tab until it has been acknowledged.

4

If you want the alarm to open in a pop-up window:

a

Select the Notifications tab.

b

Click

Add

, and then select

Add Pop-up Notification.

c

In the

Delay before pop up

field, indicate a delay, in

hours and/or minutes (HH:MM), before you want the

Advertising