Program scaling module 16, Count scale factor (count sf) 16, Rate scale factor (rate sf) 16 – Red Lion LEGEND User Manual

Page 18: Count scale multiplier (cnt.scm) 16, Rate scale multiplier (rate scm) 16, Rate conversion factor (rate per) 16

Advertising
background image

PROGRAM SCALING MODULE

In the scaling module, the Count and Rate Scale Factors, scale multipliers,

rate conversion factor, and decimal points are accessed. The following
flowchart shows only the Scaling portion:

COUNT SCALE FACTOR (COUNT SF)

The Count Scale Factor Value can range from 0.0001 to 5.9999. See

PROGRAM SCALE FACTORS MODULE for detailed description.

RATE SCALE FACTOR (RATE SF)

The Rate Scale Factor Value can range from 0.0001 to 5.9999. See

PROGRAM SCALE FACTORS MODULE for detailed description.
Note: Since the Count and Rate Scale Factors may need to be changed

periodically, they can also be accessed from the Scale Factors Module in the
main display loop.

COUNT SCALE MULTIPLIER (CNT.SCM)

There are four Count Scale Multipliers available; X 1, X 0.1, X 0.01, or X

0.001 that change the count display value accordingly. The number of pulses
counted (internal count value) is multiplied by the scale multiplier and the
scale factor values to obtain the desired Count display.
Note: Use of a small scale multiplier with a small scale factor could cause the

internal count value to be exceeded before the 6-digit display value is
exceeded.

RATE SCALE MULTIPLIER (RATE SCM)

The Rate Scale Multiplier is used with the rate scale factor and rate

conversion factor to scale the rate display value for the proper units of measure.
The scale multipliers available are; X 1, X 0.1, X 0.01, X 1000, X 100, or X 10.

RATE CONVERSION FACTOR (RATE PER)

The Rate Conversion Factor is used to display the rate value in the proper

time units of measure, per second (X1), per minute (X60), or per hour
(X3600) for the Rate display.

-16-