Once the Number of Count Edges (NCE) to be used has been determined,

the Remaining Scaling factor required, “K

R

”, can be calculated. This is the

Total Scaling, “K

T

”, divided by the Number of Count edges used as shown in

Formula #2:

FORMULA #2: K

R

= K

T

÷ NCE

WHERE:

K

R

= Remaining Scaling Factor.

K

T

= Total Scaling.

NCE = Number of Count Edges.

In our original example, the Total Scaling, “K

T

” was determined to be

0.041667. Since this value is less than one, sufficient pulse information is
being generated, i.e., there is enough resolution for the units selected. The
Number of Count edges can be left at the factory set value of X1. The Total
Scaling, “K

T

”, therefore equals the Remaining Scaling Factor, “K

R

”.

K

R

= 0.041667 ÷ 1 = 0.041667

If the remaining scaling is between 0.6000 and 5.9999, it can be

programmed directly into the Count Scale Factor value and the X1 factory
setting for the Count Scale Multiplier “SCM”, can be used.

COUNT SCALE MULTIPLIER

The general rule for choosing a SCM value is, when the Remaining Scaling

Factor, “K

R

”, is less than 0.6000, a SCM value of 0.1 or 0.01 can be used to get

a Count Scale Factor value between 0.6 and 5.9999 or to the point where the
maximum number of significant digits is obtained.

FORMULA #3: SF = K

R

÷ SCM

WHERE:

SF = Count Scale Factor.
K

R

= Remaining Scaling Factor.

SCM = Count Scale Multiplier.

Following our continuing example, it is easy to see that the Remaining

Scaling Factor, “K

R

” (0.041667), cannot fit into the Count Scale Factor Value

without losing significant digits. Using the Formula above and a Scale
Multiplier value of 0.01 allows us to get the maximum number of significant
digits possible for the Count Scale Factor value:

SF = K

R

÷ SCM = 0.041667 ÷ 0.01 = 4.1667

COUNTER SCALING EXAMPLE:

EXAMPLE #1:

A flow sensor provides 62 pulses per gallon. Calculate the scaling required

to provide a display reading in gallons. The number of “Display Units”
displayed after 62 pulses have been counted should be 1.

STEP 1 - Calculate the Total Scaling, “K

T

”, using Formula #1.

FORMULA #1:

K

T

= Display Units ÷ Number of Pulses = 1 ÷ 62 = 0.016129

STEP 2 - In this application 62 pulses per gallon provides more than enough

resolution, so the Number of Count Edges (Selected in the Program
Counter Module) is set to a value of X1. With an “NCE” value of 1, the
remaining scaling factor required is still 0.016129.

FORMULA #2

K

R

= K

T

÷ NCE = 0.016129 ÷ 1 = 0.016129

STEP 3 - To provide maximum scaling accuracy, a Scale Multiplier value is

chosen that will give the maximum amount of significant digits in the
Count Scale Factor. A value of 0.01 results in a Count Scale Factor Value
of 1.6129.

FORMULA #3

SF = K

R

÷ SCM = 0.016129 ч 0.01 = 1.6129