PROGRAM OUTPUTS MODULE (Cont’d)

OUTPUT END (RESET) MODES - OUT1 END, OUT2 END

The Output End modes operate with a timed or latched output mode. If either

output is selected as boundary, the Output End modes are NOT available.
Output End Modes apply only to outputs 1 and 2 when assigned to the Count
display. If the output is set for TIMED, the output may deactivate from timing
out or when the output end mode is reached, whichever occurs first.

OUT1 END (OUTPUT 1)

@OUT2 (Output 1 End at Output 2 Start)

Output 1 resets to its inactive state when output 2 becomes active.
This action occurs when the count equals the preset value or zero
(Reset to Preset Modes). This mode does not apply if the output is
activated by a User Input programmed for Set Output.

@OUT2END (Output 1 End at Timed Output 2 End)

Output 1 resets to its inactive state when output 2’s time delay expires.

OUT2 END (OUTPUT 2)

@ OUT1 (Output 2 End at Output 1 Start)

Output 2 resets to its inactive state when output 1 becomes active.
This action occurs when the count equals the preset value or zero
(Reset to Preset Modes). This mode does not apply if the output is
activated by a User Input programmed for Set Output.

@OUT1END (Output 2 End at Timed Output 1 End)

Output 2 resets to its inactive state when output 1’s time delay
expires.

OUTPUT POWER UP STATE ([email protected], [email protected] OR
[email protected])

Each output can be programmed individually to have the state of the output

OFF at power up ([email protected]), saved at power down ([email protected]), or ON
at power up ([email protected]). The save at power down option restores the state of
the output to what it was at power down when power is restored. The save at
power down option DOES NOT restore a timed output to the active state if the
output was active at power down. The [email protected] and [email protected] option
refers to the active state of the output, which is determined by the Output Phase.

RESET OUTPUT WITH COUNT (RST/C-EN OR DS)

If Reset with Count is enabled, the output resets with a manual reset of the

Count or Rate display. If Reset with Count is Disabled, the output does NOT
reset when a manual reset is performed on the value to which the output is
assigned.

REQUEST MESSAGE (REQMSG#—)

The selected message is requested when the output is activated. This may

be a maintained or momentary request, as selected in the Program Message
Module. A dash ‘-’ indicates that no message is to be requested. The output
must be active for a minimum of 50 msec for the request to be seen.