TROUBLESHOOTING GUIDE (Cont’d)

-61-

PROBLEMS

POSSIBLE CAUSE

REMEDIES

COUNT, PEAK, OR VALLEY
VALUES WILL NOT RESET WHEN
A MANUAL RESET IS PERFORMED

1. User Input NOT properly programmed.

1. Verify programming in “Program User Module”.

CAN NOT ENTER INTO
PROGRAMMING MENUS

1. Front panel disabled.

1. Check “Front Panel Accessible Functions With

Program Disable” section in manual.

PRESETS, COUNTER LOAD, OR
SCALE FACTORS CAN BE VIEWED

1. Front panel disabled.

1. Verify programming in “Program Options Module”

sub-menu Operator Access.

BUT NOT CHANGED

2. Check “ Front Panel Accessible Functions With

Program Disable” section of manual.

UNIT COUNTS WHILE RESET
IS ACTIVATED

1. User Input Reset mode set for Momentary reset.

1. Program User Input to a Maintained reset.

PRESET OR COUNTER LOAD VALUE
LOADS SMALLER NUMBER THAN
WHAT IS ENTERED

1. Entered number exceeds internal count capacity

(Scale multiplier/Scale factor too small).

1. Check scaling. Reduce number of pulses per unit of

measure.

OUTPUT WILL NOT RESET

1. Output assigned to wrong display (Count or Rate).

1. Verify programming in “Program Outputs Module”.

2 . R e s e t w i t h c o u n t d i s a b l e d ( P r o g r a m O u t p u t s

Module).

2. Verify programming in “Program Outputs Module”.

3. User Input NOT properly programmed.

3. Verify programming in “Program User Module”.