Type, Root, Rate – Red Lion PAX2C User Manual

Page 13: Dcpt, Ofst, Fltr, Pnts, Anlg ), Inpt, Styl

Advertising
background image

13

PROCESS INPUT TYPE

250 uA

2 U

1k RES

tc-r

r392

2.5 mA

10 U

10k RES

tc-S

r672

25 mA

25 U

tc-t

tc-b

r427

250 mA

100 U

tc-E

tc-n

2 A

200 U

tc-J

tc-C

250 mU

100 RESs

tc-k

r385

Shaded selections indicate the available process input types. Select the

desired input type.

SQUARE ROOT

YES

NO

This parameter allows the unit to be used in applications in which

the measured signal is the square of the PV. This is useful in

applications such as the measurement of flow with a differential

pressure transducer.

Example: It is necessary to square root linearize the output of a differential

pressure transmitter to indicate and control flow. The defining equation is F

= 278 ÖΔP , where ΔP = 0 - 500 PSI, transmitted linearly by a 4 - 20 mA

transducer. At full flow rate ( ΔP = 500 PSI), the flow is 6216 ft

3

/h. The

following scaling information is used with the controller:

dCPt

= 0

INPt1

= 4.00 mA

Root

= YES

dISP2

= 6216 ft

3

/hr

dISP1

= 0 ft

3

/hr

INPt2

= 20.00 mA

As a result of the scaling and square root linearization, the following

represents the readings at various inputs:

Delta P

(PSI)

Transmitter

(mA)

Flow

(ft

3

/hr)

0.00

4.00

0

15.63

4.50

1099

31.25

5.00

1554

62.50

6.00

2198

125.00

8.00

3108

187.50

10.00

3807

250.00

12.00

4396

312.50

14.00

4914

375.00

16.00

5383

437.50

18.00

5815

500.00

20.00

6216

INPUT UPDATE RATE (/SEC)

5

10

20

40

Select the ADC conversion rate (conversions per second). The

selection does not affect the display update rate, however it does

affect alarm and analog output response time. The default factory

setting of 5 is recommended for most applications. Selecting a fast update rate

may cause the display to appear very unstable.

DECIMAL RESOLUTION (Display Units)

0

to

0.000

(curr/volt/ohm)

0

to

0.0

(temp)

Select desired display resolution. The available selections are

dependent on the Input Type selected

(

tYPE

)

.

ROUNDING INCREMENT

1

2

5

10

20

50

100

Rounding selections other than one, cause the Input Display to

‘round’ to the nearest rounding increment selected (ie. rounding of

‘5’ causes 122 to round to 120 and 123 to round to 125). Rounding

starts at the least significant digit of the Input Display. Remaining

parameter entries (scaling point values, setpoint values, etc.) are not automatically

adjusted to this display rounding selection.

DISPLAY OFFSET

-1999

to

9999

The display can be corrected with an offset value. This can be used

to compensate for sensor errors, errors due to variances in sensor

placement or adjusting the readout to a reference source. A value of

zero will remove the affects of offset.

DIGITAL FILTERING

0.0

to

25.0

seconds

The input filter setting is a time constant expressed in tenths of a

second. The filter settles to 99% of the final display value within

approximately 3 time constants. This is an Adaptive Digital Filter

which is designed to steady the Input Display reading. A value of ‘0’

disables filtering.

SCALING POINTS

2

to

16

Linear - Scaling Points (2)

For linear processes, only 2 scaling points are necessary. It is

recommended that the 2 scaling points be at opposite ends of the

input signal being applied. The points do not have to be the signal

limits. Display scaling will be linear between and continue past the

entered points up to the limits of the Input Signal Jumper position. Each scaling

point has a coordinate-pair consisting of an Input Value (INPt n) and an

associated desired Display Value (dISP n).

tYPE

INP

2

U

Root

INP

NO

rAtE

INP

20

SPS

dCPt

INP

0.0

rnd

INP

0.1

OFSt

INP

0.0

FLtr

INP

1.0

SEC

PNtS

INP

2

Input

Range

Enable

Square

Root

Input

Rate

Display

Decimal

Point

Display

Rounding

Display

Offset

Value

Filter

Setting

Scaling

Points

F1

F2

P

D

Pro

N O

Pro

I N P t

INPt

P2C

A n L G

tYPE

INP

2

U

Root

INP

N O

rAtE

INP

2 0

SPS

dCPt

INP

0 . O

rnd

INP

0 . 1

OFSt

INP

0 . 0

FLtr

INP

1 . O

SEC

PNtS

INP

2

Scaling

Style

StYL

INP

K E Y

Input n

Value

INPt

INP

0 . 0

1

Display n

Value

dISP

INP

0 . O

1

Enable

Scaling

List

SLSt

INP

N O

This section details the programming for the analog input.

a

nalOg

i

npuT

p

arameTers

: p

rOCess

m

Ode

(AnLG)