arameTers

(Out)

OUTPUT SELECT

dGtL

AnLG

Select the Digital or Analog output to be programmed. The Analog

output selection only appears if an analog output and/or digital output

plug-in card is installed in the meter. When there is no output card

installed, “No Card” will be displayed on the display when trying to

enter the Output Configuration.

Out

INP

dGtL

Output

Select

Output

Assignment

Alarm Logic

Assignment

Alarm Mask

Assignment

Output

Cycle Time

F1

F2

P

D

Pro

N O

Pro

O u t

Out

P2C

d G t L

SLCt

P2C

O u t n

ASGN

On

H E A t

LGIC

On

S N G L

ASEL

Un

N O

An

CYCt

INP

2 . 0

SEC

Available when

ASGN

= ALr

n

'LJLWDO2XWSXW1XPEHU 

To have digital output capabilities, a digital output Plug-in card needs to be installed into the PAX2C (see Ordering Information). Depending on the output

card installed, there will be two or four digital outputs available.

DIGITAL OUTPUT SELECTION

Out1 Out2

Out3

Out4

Selects the digital output to be programmed. The “Outn” in the

following parameters will reflect the chosen output number. After the

chosen output is completely programmed, the display returns to the

Output Select menu. Repeat steps for each output to be programmed.

The number of outputs available is digital output card (PAXCDS)

dependent (2 or 4).

DIGITAL OUTPUT ASSIGNMENT

NONE

HEAt

COOL

ALr

MAN

This selection is used to assign the controller’s digital outputs to

various internal values or conditions. It is possible to assign the same

properties to more than one output.

NONE

= Digital Output is disabled

HEAt

= Heat Output Power

COOL

= Cool Output Power

ALr

= Alarm

MAN

= Manual Control Mode

ALARM LOGIC MODE

SNGL And

Or

The PAX2C supports three different modes when an output is

assigned as an alarm:

SNGL

= Any single alarm. Selecting YES to any selection

will change other alarm selections to NO.

And

= Allows multiple alarms to be mapped to an output

using AND Boolean logic. For example: If AL1 and

AL2 are active, the output will energize.

Or

= Allows multiple alarms to be mapped to an output

using OR Boolean logic. For example: If AL1 or

AL2 are active, the output will energize.

ALARM MASK ASSIGNMENT

NO

YES

Selects the alarms to be logically combined per the Alarm Logic

Mode selection. Any alarms configured as “YES” will be used in the

Boolean logic calculation. If the Alarm Logic Mode is assigned as

Single (SNGL), only one alarm may be selected at a time.

Basic Mode: 4 Alarms Max

Advanced Mode: 16 Alarms Max

DIGITAL OUTPUT CYCLE TIME

0.0

to

60.0

seconds

The Cycle Time value is the sum of a time-proportioned output’s

on and off cycles. With time proportional outputs, the percentage of

output power is converted into output on time of the cycle time value

eg. if the controller’s algorithm calls for 65% power, and has a Cycle

Time of 10 seconds, the output will be on for 6.5 seconds and off for

3.5 seconds. A Cycle Time equal to, or less than, one-tenth of the process time

constant is recommended.

This parameter is only available when the digital output assignment is

configured as HEAt or COOL.

SLCt

P2C

Outn

ASGN

On

HEAt

LGIC

On

SNGL

ASEL

Un

NO

An

CYCt

INP

2.0

SEC

d