Usrn, Asel, R-hi – Red Lion PAX2C User Manual

Page 16: D-lo, R-lo, R-hl, R-al, Dleu, Disp, List

Advertising
background image

16

RESET MAXIMUM DISPLAY

When activated (momentary action), rSEt flashes and

the Maximum resets to the present Input Display value.

The Maximum function then continues from that value.

This selection functions independent of the selected

display.

SELECT MINIMUM DISPLAY

The Minimum display appears on Line 2 as long as activated

(maintained). When the user input is released, the previously selected

display is returned. The

D or P keys override and disable the active

user input. The Minimum continues to function independent of the

selected display.

RESET MINIMUM DISPLAY

When activated (momentary action), rSEt flashes and

the Minimum resets to the present Input Display value.

The Minimum function then continues from that value.

This selection functions independent of the selected

display.

RESET MAXIMUM AND MINIMUM DISPLAY

When activated (momentary action), rSEt flashes and

the Maximum and Minimum readings are set to the

present Input Display value. The Maximum and Minimum

function then continues from that value. This selection

functions independent of the selected display.

RESET ALARMS

When activated (momentary action), the controller will

reset any active alarms that are selected in the User/

Function Alarm Selection Menu (ASEL).

Basic Mode: 4 Alarms Max

Advanced Mode: 16 Alarms Max

ALARM MASK SELECTION

Selects the alarms that will be reset when the User Input/

Function keys are activated. Any alarms configured as “YES”

will be reset depending on the alarms configuration. Please see

the Alarms section of the manual for more information on the

alarm reset operation.

ADJUST DISPLAY INTENSITY

When activated (momentary action), the display

intensity changes to the next intensity level.

DISPLAY SELECT

When activated (momentary action), Line 2 advances

to the next display that is not locked out from the Display

Mode.

SELECT PARAMETER LIST

Two lists of input scaling points and alarm values

(including band and deviation) are available. The two lists

are named LStA and LStb. If a user input is used to select

the list then LStA is selected when the user input is not

active and LStb is selected when the user input is active

(maintained action). If a front panel key is used to select

the list then the list will toggle for each key press

(momentary action). The display will only indicate which list is active when the

list is changed. To program the values for List-A and List-B, first complete the

programming of all the parameters. Exit programming and switch to the other

list. Re-enter programming and enter the desired values for the input scaling

points, alarms, band, and deviation if used.

PRINT REQUEST

The meter issues a block print through the serial port

when activated, and the serial type is set to rLC. The data

transmitted during a print request and the serial type is

programmed in Module 7. If the user input is still active

after the transmission is complete (about 100 msec), an

additional transmission occurs. As long as the user input

is held active, continuous transmissions occur.

USrn

FNC

r-HI

Fn

FNC

r-HI

USrn

FNC

d-Lo

USrn

FNC

r-Lo

Fn

FNC

r-Lo

USrn

FNC

r-HL

Fn

FNC

r-HL

USrn

FNC

r-AL

Fn

FNC

r-AL

ASEL

Un

NO

An

USrn

FNC

dLEU

Fn

FNC

dLEU

USrn

FNC

dISP

Fn

FNC

dISP

USrn

FNC

LISt

Fn

FNC

LISt

USrn

FNC

Prnt

Fn

FNC

Prnt

Advertising