Aln ), None, Slct – Red Lion PAX2C User Manual

Page 37: Asgn, Actn, Bdeu, Hyst, Toff, Lgic, Rset

Advertising
background image

37

a

larm

p

arameTers

(ALn)

Alarm

Assignment

Alarm

Action

Alarm

Value

Alarm

Band/Deviation

Value

Alarm

Hysteresis

Value

On Time

Delay

Off Time

Delay

Alarm

Logic

F1

F2

P

D

Pro

N O

Pro

A L r

SLCt

A L n

ASGN

An

N O N E

ACtN

An

N O

ALr

An

0 . 0

°F

bdEU

dn

0 . O

°F

HYSt

An

0 . 2

°F

tON

An

0 . 0

SEC

tOFF

An

0 . O

SEC

LGIC

An

n o r

Reset

Action

rSEt

An

A u t o

Standby

Operation

StbY

An

N O

Probe

Burn-out

Action

IFLt

An

O F F

ALARM ASSIGNMENT

NONE

PU

Selects the parameter to be used to trigger the Alarm.

NONE

= No Alarm Assignment (alarm disabled)

PU

= Input Process Value

ALARM ACTION

NO

AbHI

AbLO

AUHI

AULO

dEHI

dELO

bANd

bdIn

Enter the action for the selected alarm. See Alarm Figures for a

visual detail of each action.

NO

= No Alarm Action

AbHI

= Absolute high, with balanced hysteresis

AbLO

= Absolute low, with balanced hysteresis

AUHI

= Absolute high, with unbalanced hysteresis

AULO

= Absolute low, with unbalanced hysteresis

dEHI

= deviation high, with unbalanced hysteresis

dELO

= deviation low, with unbalanced hysteresis

bANd

= Outside band, with unbalanced hysteresis

bdIn

= Inside band, with unbalanced hysteresis

ASGN

An

NONE

ACtN

An

NO

Setpoint Alarm Figures

With reverse logic

rEv

, the below alarm states are opposite.

ALARM

STATE

OFF

ON

Hys

AL + Hys

AL

OFF

TRIGGER POINTS

ALARM

STATE

OFF

ON

Hys

AL- Bnd

AL

OFF

AL + Bnd

ON

OFF

Hys

TRIGGER POINTS

Absolute Low Acting (Unbalanced Hys) =

AULO

Band Outside Acting =

bANd

ALARM

STATE

OFF

ON

Hys

AL + ½Hys

AL

AL - ½Hys

OFF

TRIGGER POINTS

ALARM

STATE

OFF

ON

Hys

AL + Dev

AL

OFF

TRIGGER POINTS

ALARM

STATE

ON

OFF

Hys

AL - Bnd

AL

ON

AL + Bnd

OFF

ON

Hys

TRIGGER POINTS

Absolute Low Acting (Balanced Hys) =

AbLO

Deviation High Acting (Dev

> 0) =

dEHI

Band Inside Acting =

bdIn

ALARM

STATE

OFF

ON

Hys

AL

AL - Hys

OFF

TRIGGER POINTS

ALARM

STATE

OFF

ON

Hys

AL - Dev

AL

OFF

TRIGGER POINTS

ALARM

STATE

ON

OFF

Hys

AL + (-Dev)

AL

ON

TRIGGER POINTS

Absolute High Acting (Unbalanced Hys) =

AUHI

Deviation Low Acting (Dev > 0) =

dELO

Deviation High Acting (Dev

< 0) =

dEHI

ALARM

STATE

OFF

ON

Hys

AL + ½Hys

AL

AL - ½Hys

OFF

TRIGGER POINTS

Absolute High Acting (Balanced Hys) =

AbHI

Please see the Digital Output Parameter’s Configuration area for

more information about mapping an alarm to a digital output.

Advertising