Troubleshooting guide – Red Lion PAX2C User Manual

Page 52

Advertising
background image

52

TROUBLESHOOTING GUIDE

PROBLEM

REMEDIES

No Display At Power-Up

Check power level and power connections

No Display After Power-Up

Check

dLEU

and

dCnt

program settings in the Display menu.

Program Locked-Out

Check for Active User Input, programmed for

PLOC

. Deactivate User Input.

Enter proper access code at

COdE 0

prompt.

No Line 1 Display

Check program settings for Line 1 Display Assignment.

No Line 2 Display

Check program settings for Line 2 Value Access. Confirm at least one Line 2

Parameter Value is enabled in Main Display Loop.

No Programmable Units Display

Check program settings for Line 1/2 Units Mnemonic(s).

Incorrect Process Display Value

Check Input Jumper Setting, Input Level, and Input Connections.
Verify Input Menu settings.
Contact factory

Display of

OLOL

,

ULUL

,

Short

,

OPEN

, or “

. . . .

See General Controller Specifications, Display Messages.

Modules or Parameters Not Accessible

Check for corresponding plug-in option card.
Verify parameter is valid in regard to previous program settings.

Error Code:

EkEY

Keypad is active at power up. Check for depressed or stuck keypad. Press

any key to clear Error Code.

Error Code:

EPAr

Error Code:

EdYn

Parameter Data Checksum Error. Press any key to clear Error Code, verify

all program settings and cycle power. Contact factory if Error Code returns at

next power-up.

Error Code:

EPro

Parameter Data Validation Error. Press any key to clear Error Code, verify all

program settings and cycle power. Contact factory if Error Code returns at

next power-up.

Error Code:

ECAL

Calibration Data Validation Error. Contact factory.

Error Code:

ELin

Linear Output Card Data Validation Error. Press any key to clear Error Code

and cycle power. If Error Code returns at next power-up, replace Linear

Option Card or contact factory.

Advertising