1.0 i

nsTalling

The

C

OnTrOller

2.0 s

eTTing

The

J

umpers

Installation

The PAX2C meets NEMA 4X/IP65 requirements when properly installed.

The unit is intended to be mounted into an enclosed panel. Prepare the panel

cutout to the dimensions shown. Remove the panel latch from the unit. Slide the

panel gasket over the rear of the unit to the back of the bezel. The unit should

be installed fully assembled. Insert the unit into the panel cutout.

While holding the unit in place, push the panel

latch over the rear of the unit so that the tabs of

the panel latch engage in the slots on the

case. The panel latch should be

engaged in the farthest forward slot

possible. To achieve a proper

seal, tighten the latch

screws evenly until the unit is snug in the panel (Torque to approximately 7

in-lbs [79N-cm]). Do not over-tighten the screws.

Installation Environment

The unit should be installed in a location that does not exceed the operating

temperature and provides good air circulation. Placing the unit near devices that

generate excessive heat should be avoided.

The bezel should only be cleaned with a soft cloth and neutral soap product.

Do NOT use solvents. Continuous exposure to direct sunlight may accelerate the

aging process of the bezel.

Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the

keypad of the unit.

PANEL

LATCHING

SLOTS

BEZEL

PANEL

GASKET

PANEL

LATCH

LATCHING

TABS

PANEL

MOUNTING

SCREWS

-.00

(92 )

-.0

+.8

3.62

+.03

(45 )

1.77

-.0

+.5

-.00

+.02

HORIZONTAL PANEL CUT-OUT

The PAX2C controller has four jumpers that must be checked and/or changed

prior to applying power. The following Jumper Selection Figures show an

enlargement of the jumper area.

To access the jumpers, remove the controller base from the case by firmly

squeezing and pulling back on the side rear finger tabs. This should lower the

latch below the case slot (which is located just in front of the finger tabs). It is

recommended to release the latch on one side, then start the other side latch.

Warning: Exposed line voltage exists on the circuit boards. Remove

all power to the controller and load circuits before accessing inside

of the controller.

INPUT RANGE JUMPERS

Voltage Input

Two jumpers are used in configuring the controller for voltage/resistance.

The first jumper, T/V, must be in the V (voltage) position. The second jumper is

used to select the proper voltage input range. (This jumper is also used to select

the current input range.) Select a range that is high enough to accommodate the

maximum signal input to avoid overloads. For proper operation, the input range

selected in programming must match the jumper setting.

Current Input

For current input, only one jumper must be configured to select the current

range. This jumper is shared with the voltage input range. To avoid overloads,

select the jumper position that is high enough to accommodate the maximum

signal input level to be applied.

Note: The position of the T/V jumper does not matter when the controller is

in the current input mode.

Temperature Input

For temperature measurement the T/V jumper must be in the T (temperature)

position. For RTD sensors the RTD jumper must also be set.

Resistance Input

Three jumpers are used to configure the resistance input. The T/V jumper

must be in the V (voltage) position, and the excitation jumper must be in the

1.05 mA REF position. The voltage/resistance jumper position is determined by

the input range.

Excitation Output Jumper

This jumper is used to select the excitation range for the application. If

excitation is not being used, it is not necessary to check or move this jumper.

Main

Circuit

Board

REAR TERMINALS

FRONT DISPLAY

I

T

V

RTD

JUMPER

LOCATIONS

100

Finger

Tab

Finger

Tab

V

EXCITATION OUTPUT JUMPER

INPUT RANGE JUMPERS

18V @ 50mA

2V REF.

1.05 mA REF.

10 ohm RTD

100 ohm RTD

RTD INPUTS

CURRENT INPUTS

2 A

.25 A

.025 A

.0025 A

250 µA

TEMPERATURE

VOLTAGE

THERMOCOUPLE/

VOLTAGE

SELECTION

LV - 250mV/2V/100Ω/1KΩ

M - 10V/100V

HV - 25V/200V/10KΩ

VOLTAGE/RESISTANCE

INPUTS

REAR TERMINALS