Horse power limiter & anti stall with max command, Powerline user guide – High Country Tek PLD, Powerline / universal single / dual coil PWM Valve Driver User Manual

Page 22

Advertising
background image

Part No:-

021-00155 RevD7

PowerLine System Controller User Guide

Page | 22

PowerLine User Guide

MAX

MIN

Stop RPM

Slow RPM

Output

Current[A]

Output

Current[B]

Command Input

Min

MAX

Center

deadband

Horse Power Limiter & Anti Stall with Max Command


Selection from Menu ->

Control Logic-> Anti Stall w Max Command

Anti Stall w Max Command

is the same as

Anti-Stall except for the addition of the
COMMAND input that adjusts the MAX
current. The effect of the COMMAND
input is exactly the same as changing the
MAX current setting, with the adjustment
range of the analog input being the MIN to
MAX current values set by the Opto 3000

.

See the graph in figure 7.

Anti Stall w

Max Command mode can be used to give
the operator a joystick controlled load
horsepower, or load speed, adjustment in
addition to the automatic load reduction
process that prevents stalling the engine.


Figure 3 Coil Current V’s.

Command Voltages in Anti

Stall w Max Command Mode

IMPORTANT NOTE – DUAL COIL OPERATION:


The output of either ‘A’ or ‘B’ output will go from the respective ‘I Min’ setting to ZERO (0mA ) when
crossing through command mid-point. The valve outputs do NOT jump from one I Min to the other.