PowerLine System Controller User Guide

Page | 27

PowerLine User Guide


Reference Error Limits -

(active if command

error detection = true)

The Reference Error Limits feature will
detect and report errors on the Command
Reference Output of the module that
exceed the user defined set points. These
settings are used when the Command
Error Detection check box has been
checked.

High - Command Input Error reported when
reference volts are greater than High.
Low - Command Input Error reported when

reference volts are less than Low.

Auto Center
The voltage from the joystick is used during power up as the center command voltage, if it is within the Auto
Center limits set below. Check this box to enable auto center detect on power up.

Auto Center + - %
This setting is used to calculate how far a joystick can be out of

the center set point in the command range. On

power up and sets limits for the Auto Center feature.

Deadband + - %
This setting installs a Deadband over the center portion of the command voltage range that is plus and minus
percent from Command center. When the Command Input Voltage is in this range, the coil outputs are
disabled.

Auto Calibrate:

This feature is used to gather information about
the input command signal. The command range,
command error limits and reference error limits
are set automatically. The user moves the input
command to minimum and maximum, pausing
momentarily then returns to center and presses
the Ok button. The values are then stored in the
controllers temporary memory. The user must
then select the “Save Temporary Memory to
Permanent Memory” menu option to
permanently save the calibration settings.