Wesley BCT-6200-6SA User Manual

Page 37

Advertising
background image

Curtis 1243

GEN

2 Manual,

Rev. B

29

Fig. 14

The electromagnetic

brake parameters, in the
context of the 1243

GEN

2

controller’s four delay param-
eters (sequencing, interlock
brake, main contactor open,
and aux delays). This figure
assumes the standard wiring
configuration, which includes
an EM brake.

For descriptions of the
sequencing delay and main
contactor open delay, see
pages 42 and 40.

Interlock Brake Delay

(0.0 – 8.0 s)

The EM brake engages unless it already engaged

at the completion of interlock braking.

Interlock braking from motor

(applied until motor speed approx. zero)

The EM brake engages unless it already engaged

at the expiration of Intk Brake Delay.

*

The neutral state is reached when, during normal operation,

the throttle is in neutral, both direction switches are open,
and the motor speed is approximately zero.

Aux Delay

(0.0 – 30.0 s)

EM brake engages,

for Aux Types 2, 3, and 4.

INTERLOCK

SWITCH

OPENS

VEHICLE

REACHES

NEUTRAL

STATE

*

Sequencing Delay

(0.0 – 3.0 s)

HPD fault (HPD Type 1)

SRO fault

Main Open Delay

(0.0 – 40.0 s)

Main

contactor

opens

3 — PROGRAMMABLE PARAMETERS:

Electromagnetic Brake Parameters

expired or when the motor speed approaches zero, whichever occurs first. The
Interlock Brake Delay is adjustable from 0.0 to 8.0 seconds. When set to zero,
there is no delay and the brake is engaged as soon as the interlock switch opens.
Interlock braking will still occur until the motor speed hits zero.

For Aux Type 5, the interlock braking delay does not apply.

Advertising