Refrigeration installation, Hts series split system – Comfort-Aire HTS Series Split System,Two Stage, 2-5 Tons User Manual

Page 16

Advertising
background image

Figure 10: Braze Instructions

Figure 11: Air Coil Connection

Table 6: Service Valve Positions

Fully Insulated

Suction Line

Fully Insulated

Liquid Line

Nitrogen Braze

Vapor

Service ports for

gauges

CCW

CCW

Rev. 05/31/00

Replace Caps after adjusting

service valves

16

Installation, Operation & Maintenance

HTS SERIES SPLIT SYSTEM

Heat Controller, LLC

Refrigeration Installation

Position

Description

System

Service

Port

CCW - Full Out

Operation Position

Open

Closed

CCW -Full Out 1/2

turn CW

Service Position

Open

Open

CW - Full in

Shipping Position

Closed

Open

Installing the Indoor Coil and Lineset

Figure 11 shows the installation of the lineset and TXV to a
typical indoor coil. An indoor coil or air handler (fan coil) with
a TXV is required. Coils with cap tubes may not be used.
If coil includes removable fi xed orifi ce, the orifi ce must be
removed and a TXV must be installed as shown in Figure
11. Fasten the copper line set to the coil. Nitrogen should
be circulated through the system at 2-3 psi [13.8-20.7 kPa]
to prevent oxidation inside the refrigerant tubing. Use a low
silver phos-copper braze alloy on all brazed connections.

Add-On Heat Pump Applications

The HWG Series indoor coil should be located in the supply
side of the furnace to avoid condensation damage to the
furnace heat exchanger for add-on heat pump applications. A
high temperature limit switch should be installed as shown in
Figures 12b and 13b just upstream of the coil to de-energize
the compressor any time the furnace is energized to avoid
blowing hot air directly into the coil, elevating refrigerant
pressures during operation. The heat pump will trip out on
high pressure lockout without some method of disengaging
the compressor during furnace operation. Alternatively, some
thermostats with “dual fuel” mode will automatically de-
energize the compressor when second stage (backup) heat is
required.

The TXV should be brazed into place as shown in Figure 11,
keeping the “IN” side toward the compressor section. The
TXV has an internal check valve and must be installed in the
proper direction for operation. Always keep the valve body
cool with a brazing shield and wet rags to prevent damage to
the TXV. Attach the bulb to the suction line using the supplied
hose clamp. Be careful not to overtighten the clamp and
deform the bulb.

NOTICE!

The air coil should be thoroughly washed with a

fi lming agent, (dishwasher detergent like Cascade) to help
condensate drainage. Apply a 20 to 1 solution of detergent
and water. Spray both sides of coil, repeat and rinse
thoroughly with water.

Evacuation and Charging the Unit

LEAK TESTING

- The refrigeration line set must be

pressurized and checked for leaks before evacuating and
charging the unit. To pressurize the line set, attach refrigerant
gauges to the service ports and add an inert gas (nitrogen or
dry carbon dioxide) until pressure reaches 60-90 psig [413-
620 kPa]. Never use oxygen or acetylene to pressure test.
Use a halogen leak tester or a good quality bubble solution
to detect leaks on all connections made in the fi eld. Check
the service valve ports and stem for leaks. If a leak is found,
repair it and repeat the above steps. For safety reasons do
not pressurize system above 150 psig [1034 kPa]. System is
now ready for evacuation and charging.

TXV (‘IN’ toward

compressor section)

Suction Line

Liquid Line

Bulb

(Must be

Installed and
Insulated)

Equalizer

Line

TXV has internal

check valve

FP2

Sensor

Advertising