Electrical - thermostat wiring, Caution, Hts series split system – Comfort-Aire HTS Series Split System,Two Stage, 2-5 Tons User Manual

Page 25

Advertising
background image

25

Installation, Operation & Maintenance

HTS SERIES SPLIT SYSTEM

Heat Controller, LLC

Thermostat Installation

The thermostat should be located on an interior wall in a
larger room, away from supply duct drafts. DO NOT locate
the thermostat in areas subject to sunlight, drafts or on
external walls. The wire access hole behind the thermostat
may in certain cases need to be sealed to prevent erroneous
temperature measurement. Position the thermostat back
plate against the wall so that it appears level and so the
thermostat wires protrude through the middle of the back
plate. Mark the position of the back plate mounting holes and
drill holes with a 3/16” (5mm) bit. Install supplied anchors and
secure plate to the wall. Thermostat wire must be 18 AWG
wire. Wire the appropriate thermostat as shown in Figure 24
or 25 to the low voltage terminal strip on the DXM2 control
board. Practically any heat pump thermostat will work with
these units, provided it has the correct number of heating
and cooling stages.

Thermostat

DXM2

Board

Y1
Y2

W

H

O
G
R
C

AL1

Air

Handler

Non-AXM

Air Handler

Y1
Y2

W

H

O
G
R
C

AL1

Compressor

Compressor Stage

Reversing Valve

Fan

24Vac Hot

24Vac Common

Fault LED

Y1
Y2

W

DH

O
G
R

C

L

Dehumidificatio

Auxiliary Heat

Notes:
1) ECM auomatic dehumidification mode operates with dehumidification airflows in the cooling
mode when the dehumidification output from thermostat is active. Normal heating and cooling
airflows are not affected.
2) DXM2 board DIP switch S2-7 must be in the auto dehumidification mode for automatic
dehumidification.

Figure 25: Conventional 3 Heat / 2 Cool Thermostat

Connection to DXM2 and Non-AXM Air Handler

CAUTION!

CAUTION!

Refrigerant pressure activated water regulating

valves should never be used with Heat Controller
equipment.

Electrical - Thermostat Wiring

CAUTION!

CAUTION!

Either a communicating thermostat (7602-

443) or confi guration tool (7602-444) MUST be used to
confi gure and diagnose this unit.

Thermostat Connections

C

24V Common for Control Circuit

R

24V Supply for Control Circuit

A+ Communications

(Positive)

B –

Communications (Negative)

GND Ground
OD Outdoor

Temperature

Sensor

ID Indoor

Temperature

Sensor

ATC32U** Thermostat

Unit with

AXM

Control

24Vac Hot

DXM2

Control

24V

Comm +

A+

A+

Comm -

B-

B-

OD

ID

GND

Outdoor

Sensor

(Optional)

Remote Indoor

Sensor

(Optional)

24Vac Common

Gnd

R

C

24V

A+

B-

Gnd

7602-443

WDG

Figure 24: Communicating Thermostat Connection to
DXM2 Control