Unit start-up and operating conditions, Caution! caution – Comfort-Aire HTS Series Split System,Two Stage, 2-5 Tons User Manual

Page 30

Advertising
background image

30

Installation, Operation & Maintenance

HTS SERIES SPLIT SYSTEM

Heat Controller, LLC

Unit Start-Up and Operating Conditions

Unit and System Checkout

BEFORE POWERING SYSTEM, please check the following:

UNIT CHECKOUT

Shutoff valves: Insure that all isolation valves are open.
Line voltage and wiring: Verify that voltage is within an

acceptable range for the unit and wiring and fuses/
breakers are properly sized. Verify that low voltage wiring is
complete.

Unit control transformer: Insure that transformer has the

properly selected voltage tap. Residential 208-230V units
are factory wired for 230V operation unless specifi ed
otherwise.

Loop/water piping is complete and purged of air. Water/

piping is clean.

Antifreeze has been added if necessary.
Entering water and air: Insure that entering water and air

temperatures are within operating limits of Tables 9a and
9b.

Low water temperature cutout: Verify that low water

temperature cut-out on the DXM2 control is properly set.

Unit fan: Manually rotate fan to verify free rotation and

insure that blower wheel is secured to the motor shaft. Be
sure to remove any shipping supports if needed. DO NOT
oil motors upon start-up. Fan motors are pre-oiled at the
factory. Check unit fan speed selection and compare to
design requirements.

Condensate line: Verify that condensate trap is installed

and pitched.

HWG pump is disconnected unless piping is completed

and air has been purged from the system.

Water

fl ow balancing: Record inlet and outlet water

temperatures for each heat pump upon startup. This check
can eliminate nuisance trip outs and high velocity water
fl ow that could erode heat exchangers.

Unit air coil and fi lters: Insure that fi lter is clean and

accessible. Clean air coil of all manufacturing oils.

Unit controls: Verify that DXM2 fi eld selection options are

properly set. Low voltage wiring is complete.

Blower CFM and Water ∆T is set on communicating

thermostats or diagnostic tool.

Service/access panels are in place.

SYSTEM CHECKOUT

System water temperature: Check water temperature for

proper range and also verify heating and cooling set points
for proper operation.

System pH: Check and adjust water pH if necessary to

maintain a level between 6 and 8.5. Proper pH promotes
longevity of hoses and fi ttings (see Table 4).

System

fl ushing: Verify that all air is purged from the

system. Air in the system can cause poor operation or
system corrosion. Water used in the system must be
potable quality initially and clean of dirt, piping slag,
and strong chemical cleaning agents. Some antifreeze
solutions may require distilled water.

Internal Flow Controller: Verify that it is purged of air and in

operating condition.

CAUTION!

CAUTION!

CAUTION!

To avoid equipment damage, DO NOT

leave system fi lled in a building without heat during the
winter unless antifreeze is added to the water loop. Heat
exchangers never fully drain by themselves and will freeze
unless winterized with antifreeze.

CAUTION!

Verify that ALL water valves are open and

allow water fl ow prior to engaging the compressor.
Freezing of the coax or water lines can permanently
damage the heat pump.

Unit Start-up Procedure

1. Turn the thermostat fan position to “ON.” Blower

should start.

2. Balance air fl ow at registers.
3. Adjust all valves to their full open position. Turn on the line

power to all heat pump units.

4. Room temperature should be within the minimum-

maximum ranges of Table 9b. During start-up checks,
loop water temperature entering the heat pump should be
between 30°F [-1°C] and 95°F [35°C].

5. It is recommended that water-to-air units be fi rst started

in the cooling mode, when possible. This will allow liquid
refrigerant to fl ow through the fi lter-drier before entering
the TXV, allowing the fi lter-drier to catch any debris that
might be in the system before it reaches the TXV.

6. Two factors determine the operating limits of geothermal

heat pumps, (a) return air temperature, and (b) water
temperature. When any one of these factors is at a
minimum or maximum level, the other factor must be at
normal level to insure proper unit operation.

6. Two factors determine the operating limits of geothermal

heat pumps, (a) return air temperature, and (b) entering
water temperature. When either of the factors is at a
minimum or maximum level, the other factor must be at
normal levels to insure proper unit operation.

a. Place the unit in Manual Operation. When in manual

mode activate Y1,Y2, and O to initiate the cooling
mode. Also manually increase CFM until desired
cooling CFM is achieved. Next adjust pump speed
% until desired loop temperature difference (leaving
water temperature minus entering water temperature)
is achieved. (For modulating valve adjust valve %).

System controls: Verify that system controls function and

operate in the proper sequence.

Low water temperature cutout: Verify that low water

temperature cut-out controls are set properly
(LT1 - JW3).

Miscellaneous: Note any questionable aspects of

the installation.

Advertising