Electrical - low voltage, Dxm2 pcb, Hts series split system – Comfort-Aire HTS Series Split System,Two Stage, 2-5 Tons User Manual

Page 24: Installation, operation & maintenance, Heat controller, llc, Figure 23: lt1 limit setting, Figure 23a: accessory wiring

Advertising
background image

24

Installation, Operation & Maintenance

HTS SERIES SPLIT SYSTEM

Heat Controller, LLC

Figure 23: LT1 Limit Setting

Comp

Relay

24Vdc

EH1
EH2

P6

Off On

JW3

c1

ay

c2

ay

CO

RV

RV

LT1
LT1
LT2
LT2

LP

P7

CC

CCG

CO

S1

S2

12

1

4

Off On

AO2

P11

Gnd

T1

P10

T2 T2 T3

T3 T4 T4

T5

P9

T5 T6 T6

A0-1 A0-2

Off On

S3

RV

Relay

CCH

Relay

1 2 3 4

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

DXM2 PCB

JW3-LT1

jumper should

be clipped

for low

temperature

(antifreeze)

operation

Accessory Connections

A terminal paralleling the compressor contactor coil has been
provided on the DXM2 control. Terminal “A” is designed to
control accessory devices. Note: This terminal should be used
only with 24 Volt signals and not line voltage. Terminal “A” is
energized with the compressor contactor.

Figure 22: HTS Low Voltage Field Wiring

Low Water Temperature Cutout Selection

The DXM2 control allows the fi eld selection of low water (or
water-antifreeze solution) temperature limit by clipping jumper
JW3, which changes the sensing temperature associated
with thermistor LT1. Note that the LT1 thermistor is located
on the refrigerant line between the coaxial heat exchanger
and expansion device (TXV). Therefore, LT1 is sensing
refrigerant temperature, not water temperature, which is
a better indication of how water fl ow rate/temperature is
affecting the refrigeration circuit.

The factory setting for LT1 is for systems using water (30°F
[-1.1°C] refrigerant temperature). In low water temperature
(extended range) applications with antifreeze (most ground
loops), jumper JW3 should be clipped as shown in Figure
23 to change the setting to 10°F [-12.2°C] refrigerant
temperature, a more suitable temperature when using
an antifreeze solution. All residential units include water/
refrigerant circuit insulation to prevent internal condensation,
which is required when operating with entering water
temperatures below 59°F [15°C].

Electrical - Low Voltage

Figure 23a: Accessory Wiring

24VAC

DXM2

P2

C

A

Terminal Strip

Motorized Modulating Water Control Valve - Open Loop
Ground Water Systems Only

An external valve should be used on ground water systems
to shut off fl ow when the compressor is not operating. Valve
kit AMMV4D is available for use with HTS024-048, and kit
AMMV5E is used with HTS060. See Figure 23b or the unit
wiring diagram for valve wiring detail. Further details on valve
operation are described later in this manual.

Figure 23b: Motorized Modulating Water Control Valve -
Open Loop Ground Water Systems Only

DXM 2

P11

P3

For MWV option, place jumper on 0-10V pins.
Ensure actuator direction switch is set as shown.

Low Voltage Field Wiring