The hot water generator pump power wiring is disabled at
the factory to prevent operating the HWG pump “dry.” After
all HWG piping is completed and air purged from the water
piping, the pump power wires should be applied to terminals
on the HWG power block PB2 as shown in the unit wiring
diagram. This connection can also serve as a HWG disable
when servicing the unit.

23

Installation, Operation & Maintenance

HTS SERIES SPLIT SYSTEM

Heat Controller, LLC

Figure 21: R-410A Compressor Section Line Voltage
Field Wiring

Electrical - Line Voltage

Electrical - Line Voltage

All fi eld installed wiring, including electrical ground, must
comply with the National Electrical Code as well as all
applicable local codes. Refer to the unit electrical data for
fuse sizes. Consult wiring diagram for fi eld connections that
must be made by the installing (or electrical) contractor.

All fi nal electrical connections must be made with a length of
fl exible conduit to minimize vibration and sound transmission
to the building.

General Line Voltage Wiring

Be sure the available power is the same voltage and phase
shown on the unit serial plate. Line and low voltage wiring
must be done in accordance with local codes or the National
Electric Code, whichever is applicable.

Power Connection

Line voltage connection is made by connecting the incoming
line voltage wires to the “L” side of the contactor as shown in
Figures 21. Consult Table 7for correct fuse size.

208-230 Volt Operation

Verify transformer tap with air handler wiring diagram to
insure that the transformer tap is set to the correct voltage,
208V or 230V.

WARNING!

CAUTION!

WARNING!

To avoid possible injury or death due to

electrical shock, open the power supply disconnect switch
and secure it in an open position during installation.

CAUTION!

Use only copper conductors for fi eld installed

electrical wiring. Unit terminals are not designed to accept
other types of conductors.

Table 7: GeoMax 2 (HTS) Electrical Data

See unit wiring diagram for addtional details.

Unit Power Supply

(see electrical

table for wire and

breaker size)

Model

Compressor

HWG Pump

FLA

External

Pump FLA

Total Unit

FLA

Min Circuit

Amps

Max Fuse/

HACR

RLA

LRA

Qty

026

11.7

58.3

1

0.5

4.0

16.2

19.1

30

038

15.3

83.0

1

0.5

4.0

19.8

23.6

35

049

21.2

104.0

1

0.5

4.0

25.7

31.0

50

064

27.1

152.9

1

0.5

4.0

31.6

38.3

60

Rated Voltage of 208/230/60/1

Min/Max Voltage of 197/252

HACR circuit breaker in USA

only

All

fuses

Class RK-5