Functional troubleshooting, Hts series split system, Installation, operation & maintenance – Comfort-Aire HTS Series Split System,Two Stage, 2-5 Tons User Manual

Page 40: Heat controller, llc

Advertising
background image

40

Installation, Operation & Maintenance

HTS SERIES SPLIT SYSTEM

Heat Controller, LLC

Functional Troubleshooting

Fault

Htg Clg Possible Cause

Solution

Main Power Problems

X

X

Green status LED off

Check Line Voltage circuit breaker and disconnect
Check for line voltage between L1 and L2 on the contactor
Check for 24VAC between R and C on DXM
Check primary/secondary voltage on transformer

HP Fault Code 2

X

Reduced or no water flow

Check pump operation or valve operation/setting

in cooling

Check water flow adjust to proper flow rate

X

Water t emperature out of range in
cooling

Bring water temp within design parameters

X

Reduced or no air flow

Check for dirty air filter and clean or replace

in heating

Check fan motor operation and airflow restrictions
Dirty air coil- construction dust etc.
Too high of external static. Check static vs blower table

X

Air t emperature out of range in
heating

Bring return air temp within design parameters

X

X

Overcharged with refrigerant

Check superheat/subcooling vs typical operating condition
table

X

X

Bad HP switch

Check switch continuity and operation - Replace

LP/LOC Fault-Code 3

X

X

Insufficient charge

Check for refrigerant leaks

Low Pressure/Loss of Charge

X

Compressor pump down at start-
up

Check charge and start-up water flow

LT1 Fault - Code 4

X

Reduced or no water flow

Check pump operation or water valve operation/setting

Water Low Temperature

in heating

Plugged strainer or filter - clean or replace
Check water flow adjust to proper flow rate

X

Inadequate anti-freeze level

Check antifreeze density with hydrometer

X

Improper low temperature setting
(30°F vs 10°F)

Clip LT1 jumper for antifreeze (10°F) use

X

Water t emperature out of range

Bring water temp within design parameters

X

X

Bad thermistor

Check temp and impedance correlation per chart

LT2 Fault - Code 5
Low Air Temperature

X

Reduced or no air flow

Check for dirty air filter and clean or replace

in cooling

Check fan motor operation and airflow restrictions
Too high of external static - check static vs blower table

X

Air temperature out of range

Too much cold vent air - bring entering air temp within
design parameters

X

Improper low temperature setting
(30°F vs 10°F)

Normal airside applications will require 30°F only

X

X

Bad thermistor

Check temp and impedance correlation per chart

Condensate Fault-Code
High Condensate Level

6

X

X

Blocked drain

Check for blockage and clean drain

X

X

Improper trap

Check trap dimensions and location ahead of vent

X

Poor drainage

Check for piping slope away from unit
Check slope of unit toward outlet
Poor venting - check vent location

X

Moisture on sensor

Check for moisture shorting to air coil

Over/Under Voltage-Code 7

X

X

Under voltage

Check power supply and 24VAC voltage before and during
operation

(Auto Resetting)

Check power supply wire size
Check compressor starting. Need hard start kit?
Check 24VAC and unit transformer tap for correct power

supply voltage

X

X

Over voltage

Check power supply voltage and 24VAC before and during

operation.
Check 24VAC and unit transformer tap for correct power
supply voltage

Unit Performance
Sentinel-Code 8

X

Heating Mode LT2>125°F

Check for poor air flow or overcharged unit

X

Cooling Mode LT1>125°F OR
LT2< 40°F

Check for poor water flow, or air flow

Swapped Thermistor

Code 9

X

X

LT1 and LT2 swapped

Reverse position of thermistors

X

X

Plugged air filter

X

X

Restricted return air flow

Replace air filter
Find and eliminate rectriction - increase return duct
and/or grille size

ECM Fault - Code 10

X

X

Blower does not operate

Check blower line voltage
Check blower low voltage wiring

Blower operating with incorrect
airflow

Wrong unit size selection

Wrong unit family selection

Wrong motor size

Incorrect blower selection

High Pressure

X

Frozen water heat exchanger

Thaw heat exchanger

X

X

Bad HPWS Switch

Replace HPWS Switch