Functional troubleshooting, Hts series split system, Installation, operation & maintenance – Comfort-Aire HTS Series Split System,Two Stage, 2-5 Tons User Manual

Page 41: Heat controller, llc

Advertising
background image

41

Installation, Operation & Maintenance

HTS SERIES SPLIT SYSTEM

Heat Controller, LLC

Functional Troubleshooting

No Fault Code Shown

X

X

No compressor operation

See 'Only Fan Operates'

X

X

Compressor overload

Check and replace if necessary

X

X

Control board

Reset power and check operation

Unit Short Cycles

X

X

Dirty air filter

Check and clean air filte r

X

X

Unit in 'Test Mode'

Reset power or wait 20 minutes for auto exit

X

X

Unit selection

Unit may be oversized for space - check sizing for actual
load of space

X

X

Compressor overload

Check and replace if necessary

Only Fan Runs

X

X

Thermostat position

Insure thermostat set for heating or cooling operation

X

X

Unit locked out

Check for lockout codes - reset power

X

X

Compressor overload

Check compressor overload - replace if necessary

X

X

Thermostat wiring

Check thermostat wiring at DXM2 - put in Test Mode and

ESD - ERV Fault (DXM Only)

Green Status LED Code 3

X

X

ERV unit has fault

(Rooftop units only)

Troubleshoot ERV unit fault

jumper Y1 and R to give call for compressor

IFC Fault Code 13
Internal Flow
Controller Fault

X

X

No pump output signal

Check DC voltage between A02 and GND - should be
between 0.5 and 10 VDC with pump active

Low pump voltage

Check line voltage to the pump

No pump feedback signal

Check DC voltage between T1 and GND. Voltage should
be between 3 and 4 VDC with pump OFF, and between
0 and 2 VDC with the pump ON

Bad pump RPM sensor

Replace pump if the line voltage and control signals are
present at the pump, and the pump does not operate

Fault

Htg Clg Possible Cause

Solution