Performance Troubleshooting

Symptom

Htg Clg Possible Cause

Solution

Insufficient Capacity/

X

X

Dirty filter

Replace or clean

Not Cooling or Heating

Rduced or no air flow

Check for dirty air filter and clean or replace

Properly

in heating

Check fan motor operation and airflow restrictions
Too high of external static - check static vs blower table

Reduced or no air flow

Check for dirty air filter and clean or replace

in cooling

Check fan motor operation and airflow restrictions
Too high of external static - check static vs blower table

X

X

Leaky duct work

Check supply and return air temperatures at the unit and at
distant duct registers if significantly different, duct leaks
are present

X

X

Low refrigerant charge

Check superheat and subcooling per chart

X

X

Restricted metering device

Check superheat and subcooling per chart - replace

X

Defective reversing valve

Perform RV touch test

X

X

Thermostat improperly located

Check location and for air drafts behind stat

X

X

Unit undersized

Recheck loads & sizing check sensible clg load and heat
pump capacity

X

X

Scaling in water heat exchanger

Perform Scaling check and clean if necessary

X

X

Inlet water too hot or cold

Check load, loop sizing, loop backfill, ground moisture

High Head Pressure

X

Reduced or no air flow

Check for dirty air filter and clean or replace

in heating

Check fan motor operation and airflow restrictions

Too high of external static - check static vs blower table

X

Reduced or no water flow

Check pump operation or valve operation/setting

in cooling

Check water flow adjust to proper flow rate

X

Inlet w ater too hot

Check load, loop sizing, loop backfill, ground moisture

X

Air temperature out of range in
heating

Bring return air temp within design parameters

X

Scaling in water heat exchanger

Perform Scaling check and clean if necessary

X

X

Unit over charged

Check superheat and subcooling - reweigh in charge

X

X

Non-condensables insystem

Vacuum system and reweigh in charge

X

X

Restricted metering device

Check superheat and subcooling per chart - replace

Low Suction Pressure

X

Reduced water flow

Check pump operation or water valve operation/setting

in heating

Plugged strainer or filter - clean or replace
Check water flow adjust to proper flow rate

X

Water temperature out of range

Bring water temp within design parameters

X

Reduced air flow

Check for dirty air filter and clean or replace

in cooling

Check fan motor operation and airflow restrictions
Too high of external static - check static vs blower table

X

Air temperature out of range

Too much cold vent air - bring entering air temp within
design parameters

X

X

Insufficient charge

Check for refrigerant leaks

Low Dischage Air
Temperature in Heating

X

Too high of air flow

Check fan motor speed selection and airflow chart

X

Poor performance

See “Insufficient Capacity”

High Humidity

X

Too high of air flow

Check fan motor speed selection and airflow chart

X

Unit oversized

Recheck loads and sizing check sensible clg load and
heat pump capacity

Only Compressor Runs

X

X

Thermostat wiring

Check G wiring at heat pump. Jumper G and R for fan
operation.

X

X

Fan motor relay

Jumper G and R for fan operation. Check for Line voltage
across blower relay contacts.
Check fan power enable relay operation (if present)

X

X

Fan motor

Check for line voltage at motor. Check capacitor

X

X

Thermostat wiring

Check thermostat wiring at or DXM2. Put in Test Mode
and then jumper Y1 and W1 to R to give call for fan,
compressor and electric heat.

Unit Doesn't Operate in

Cooling

X

Reversing Valve

Set for cooling demand and check 24VAC on RV coil.
If RV is stuck, run high pressure up by reducing water flow
and while operating engage and disengage RV coil voltage
to push valve.

X

Thermostat setup

X

Thermostat wiring

Check O wiring at heat pump. DXM2 requires call for
compressor to get RV coil “Click.”

X

X

Modulating Valve
Troubleshooting

X

Improper output setting

Verify the AO-2 jumper is in the 0-10V position

No valve operation

Check voltage to the valve

X

No valve output signal

Check DC voltage between AO2 and GND. Should be O
when valve is off and between 3.3v and 10v when valve
is on.

Replace valve if voltage and control signals are present at
the valve and it does not operate

For DXM2 check for “O” RV setup not “B”.