39

Installation, Operation & Maintenance

HTS SERIES SPLIT SYSTEM

Heat Controller, LLC

DXM2 Process Flow Chart

WARNING!

WARNING!

HAZARDOUS VOLTAGE! DISCONNECT

ALL ELECTRIC POWER INCLUDING REMOTE
DISCONNECTS BEFORE SERVICING.
Failure to disconnect power before servicing can cause
severe personal injury or death.

See “ Does

not Operate

in Clg”

See “ Only

Comp

Runs”

Start

Did Unit

Attempt to

Start?

Did Unit

Lockout at

Start-up?

Unit Short

Cycles?

Only Fan

Runs?

Only

Compressor

Runs?

Did unit lockout

after a period of

operation?

Does unit

operate in

cooling?

Unit is OK!

‘See Performance

Troubleshooting’ for

further help

Check Main

power (see power

problems)

Check fault code on communicating

thermostat (ATC32) or Configuration

and Diagnostics Tool (ACD01)

Yes

No

No

No

No

No

Yes

No

Yes

See fault codes in table

on following page

No fault

shown

Replace

DXM2

See “ Unit

short

cycles”

See “ Only

Fan Runs”

No

Yes

Yes

Yes

Yes

DXM2 Functional

Troubleshooting Flow Chart

Check fault code on

communicating thermostat or

Confi guration and Diagnostics Tool