1 cpx-specific leds, Cpx−specific leds, 1 cpx−specific leds – Festo Электрический терминал СРХ User Manual

Page 30

Advertising
background image

1. System summary

1−14

Festo P.BE−CPX−CEC−EN en 1004a

1.5.1

CPX−specific LEDs

The displays of the CPX−specific LEDs are described in the
following. Information on the controller LEDs can be found in
section 4.2.

PS (Power System) ć supply to the electronics

LED (green)

Sequence

Meaning

Error treatment

LED lights up

ON

OFF

No error. Operating voltĆ
age/sensor supply applied

ć

LED flashes

ON

OFF

Operating voltage/sensor
supply outside the tolerĆ
ance range

Eliminate undervoltage

LED flashes

ON

OFF

Internal fuse for the
operating voltage/sensor
supply has responded

1. Eliminate short circuit/overload on

module side

2. Depends on the parameterisation

of the module (module parameter):

·

The sensor supply voltage will
be switched on again

automatiĆ

cally when the short circuit has
been eliminated (default)

·

Power OFF/ON is necessary

LED is off

ON

OFF

The operating voltage/
sensor supply is not
applied

Check the operating voltage
connection of the electronics

Tab. 1/4:

Displays of PS LED

Advertising