Festo Электрический терминал СРХ User Manual
Page 80

A. Technical appendix
A−4
Festo P.BE−CPX−CEC−E N en 1004a
CPX−CEC/CPX−CEC−...
LED display (product−specific)
RUN:
PLC status: started
STOP:
PLC status: stopped
ERR:
PLC run−time error
PS:
Electronic supply,
sensor supply
PL:
Load supply
SF:
System fault
M:
Modify/forcing active
Fieldbus interface (CPX−CEC−C1/−M1)
Ĉ Type
Ĉ Connection technology
Ĉ CPX−CEC−C1 transmission rate
Ĉ CPX−CEC−M1 transmission rate
Ĉ Electrical isolation
CAN bus
Plug, Sub−D, 9−pin
125; 250; 500; 800; 1,000 kbps
(adjust. via software)
125; 250; 500; 1,000 kbps
(adjust. via software)
Yes
Data interface (CPX−CEC)
Ĉ Type
Ĉ Connection technology
Ĉ Transmission speed
Ĉ Electrical isolation
RS232 interface
Socket, Sub−D, 9−pin
9.6 ... 230.4 kbps
Yes
Ethernet
Ĉ Number
Ĉ Connector plug
Ĉ Transmission speed
Ĉ Supported protocols
1
RJ45, socket, 8−pin
10/100 mbps
TCP/IP, EasyIP, Modbus TCP
Protection class
only in conjunction with plugs and covers in
protection class IP65/IP67
IP65/IP67
Nominal operating voltage
24 V DC
Load voltage
Ĉ without pneumatics
Ĉ with pneumatics type Midi/Maxi
Ĉ with pneumatics type CPA
Ĉ with pneumatics type MPA
18 ... 30 V DC
21.6 ... 26.4 V DC
20.4 ... 26.4 V DC
18 ... 30 V DC
Intrinsic current consumption
Ĉ at rated voltage
Typically 85 mA