Operating Instructions Temperature Indicating Controller CS4H / CS4L

V1.1

•

05/2006

- 19 -

5.2 Main setting mode

If the MODE key is pressed, main setting mode is selected.
The setting value (numeric value) can be increased or decreased by pressing the

▲

or

▼

key.

If the MODE key is pressed, the setting value is registered and the controller will revert to the PV/SV
display mode.

SV1 [ ]
• Sets SV1.
• Setting range: SV low limit to SV high limit or

Scaling low limit value to Scaling high limit value

• Default: 0 °C

SV2 [

]

• Sets SV2.
• Setting range: SV low limit to SV high limit or

Scaling low limit value to Scaling high limit value

• Default: 0 °C


5.3 Sub setting mode

By pressing the MODE key while holding down the

▲

key, Sub setting mode can be selected.

The

▲

or

▼

key increases or decreases the setting value (numeric value).

By pressing the MODE key, setting value is registered and the next setting item is selected.

AT setting/ Auto-reset setting [

/

]

• Sets AT (Auto-tuning) or Auto-reset (offset correction).
• Auto-reset can be performed only during PD and P action.

(Not available for PID, PI and ON/OFF action)

• Default: Both Auto-tuning and Auto-reset Cancellation
[Auto-tuning]
• If the auto-tuning performance is designated, AT indicator blinks and the controller reverts to the

PV/SV display mode.

• After auto-tuning ends, AT indicator is turned off and P, I, D and ARW values are automatically

set.

• During auto-tuning, none of the settings can be performed.
• If the auto-tuning is released during the process, P, I, D and ARW values revert to their former

value.

• If the

OUT

/

OFF

key is pressed during auto-tuning, control output OFF function is activated, and if the

OUT

/

OFF

key is pressed again, PID auto-tuning is cancelled.

[Auto-reset]
• If the auto-reset is performed, offset correction immediately starts and the controller reverts to

the PV/SV display mode. (The corrected value is automatically set and AT indicator blinks)

• During 4 minutes of auto-reset performing, other settings cannot be performed to prevent key

misoperations.

• After auto-reset ends, AT indicator is turned off and all settings can be carried out.

OUT1 proportional band setting [ ]
• Sets OUT1 proportional band.

ON/OFF action when set to 0 or 0.0.

• Setting range: 0 … 1000 °C (0 … 2000 °F)

With a decimal point: 0.0 … 999.9 °C (0.0 … 999.9 °F)
DC input: 0.0 … 100.0 %

• Default: 10 °C
OUT2 proportional band setting [

]

• Sets OUT2 proportional band.

ON/OFF action when set to 0 or 0.0.

• Not available when 2. control output (option) is not applied or when OUT1 is ON/OFF action
• Setting range: 0.0 … 10.0 times (multiplying factor to OUT1 proportional band)
• Default: 1.0 times