Operating Instructions Temperature Indicating Controller CS4H / CS4L

V1.1

05/2006

- 38 -

8.2 PID auto-tuning of this controller

In order to decide each value of P, I, D and ARW automatically, this system forcibly fluctuates the object
being controlled.

(1) When the difference between the setting value and processing temperature is large as the

temperature rises.

Fluctuation is applied at the temperature 20 °C lower than the setting value.

(1) Calculating PID con-

stant

(2) PID constant

calculated

(3) Controlled by the PID

constant set by auto-

tuning.

(4) AT bias value


(Fig.

8.2-1)

(2) When the control is stable or when control temperature is within ±20 °C (°F) of setting value.

Fluctuation is applied at the setting value.

(1) Calculating PID con-

stant

(2) PID constant

calculated

(3) Controlled by the PID

constant set by

auto-tuning.



(Fig.

8.2.2)

(3) When the control temperature is 20 °C (°F) or higher than the setting value.

Fluctuation is applied at the temperature 20 °C (°F) higher than the setting value.


(1) Calculating PID const

ant

(2) PID constant calculat

ed

(3) Controlled by the PID

constant set by auto-t
uning.

(4) AT bias value


(Fig.

8.2.3)

Temperature 20 °C (°F) lower than the setting value

Temperature 20 °C (°F) higher than the setting value

(1)

(2)

(3)

(4)

AT starting point

Setting

value

Temperature

Time

AT starting point

(1)

(2)

(3)

Temperature

Setting

value

Time

AT starting point

(1)

(2)

(3)

(4)

Temperature

Setting

value

Time