Operating Instructions Temperature Indicating Controller CS4H / CS4L

V1.1

05/2006

- 23 -

Data transfer rate selection [

]

• Selects the data transfer rate of this unit. (The data transfer rate of this unit must be equal to the

rate of the host computer, otherwise it is impossible to communicate)

• Available only when the option Serial interface [CR5] is applied
• Selection items:

(2400 bps)

(4800 bps)

(9600 bps)

(19200 bps)

• Default: 9600 bps
Parity selection [

]

• Selects the parity of this unit.
• Not available when the option Serial interface [CR5] is not applied or when WIKA protocol is

selected in the Communication protocol selection

• Selection item:

(WIKA protocol)

(Modbus RTU mode)

(Modbus ASCII mode)

• Default: WIKA protocol
Stop bit selection [

]

• Selects the stop bit of this unit.
• Not available when the option Serial interface [CR5] is not applied or when WIKA protocol is

selected in the Communication protocol selection

• Selection item: (1)

(2)

• Default: 1