Operating Instructions Temperature Indicating Controller CS4H / CS4L

V1.1

•

05/2006

- 24 -


5.5 Auxiliary function setting mode 2

In the PV/SV display mode, if the MODE key is pressed while the

▲

and

▼

keys are being pressed for

approx. 3 seconds, Auxiliary function setting mode 2 can be selected.
The setting value can be increased or decreased by pressing the

▲

or

▼

key.

If the MODE key is pressed, the setting value is registered and the next setting item is selected.
If Lock 3 is selected in the Setting value lock selection, release Lock 3 to Unlock, and then change
each setting value in the Auxiliary function setting mode 2.

Sensor selection [

]

• An input type from thermocouple (10 types), RTD (2 types), DC current (2 types),

DC voltage (4 types) and the unit °C/°F can be selected.

• When changing the input from DC voltage to other inputs, remove the sensor con-

nected to this controller, then change for the input. If the input is changed with the
sensor connected, the input circuit may be broken.

• Default: K (–200 … 1370 °C)

Input type

Input range

–200 … 1370 °C:

–320 … 2500 °F:

K

–199.9 … 400.0 °C:

–199.9 … 750.0 °F:

J

–200 … 1000 °C:

–320 … 1800 °F:

R

0 … 1760 °C:

0 … 3200 °F:

S

0 … 1760 °C:

0 … 3200 °F:

B

0 … 1820 °C:

0 … 3300 °F:

E

–200 … 800 °C:

–320 … 1500 °F:

T

–199.9 … 400.0 °C:

–199.9 … 750.0 °F:

N

–200 … 1300 °C:

–320 … 2300 °F:

PL-

0 … 1390 °C:

0 … 2500 °F:

C(W/Re5-26)

0 … 2315 °C:

0 … 4200 °F:

Pt100

–199.9 … 850.0 °C:

–199.9 … 999.9 °F:

Pt100

–200 … 850 °C:

–300 … 1500 °F:

JPt100

–199.9 … 500.0 °C:

–199.9 … 900.0 °F:

JPt100

–200 … 500 °C:

–300 … 900 °F:

4 … 20 mA DC

–1999 … 9999:

0 … 20 mA DC

–1999 … 9999:

0 … 1 V DC

–1999 … 9999:

0 … 5 V DC

–1999 ... 9999:

1 … 5 V DC

–1999 … 9999:

0 … 10 V DC

–1999 … 9999:

Scaling high limit setting [

]

• Sets scaling high limit value.
• Available only for the DC input
• Setting range: Scaling low limit value to Input range high limit value

(The placement of the decimal point follows the selection.)

• Default: 9999
Scaling low limit setting [

]

• Sets scaling low limit value.
• Available only for the DC input
• Setting range: Input range low limit value to scaling high limit value

(The placement of the decimal point follows the selection.)

• Default: –1999