Operating Instructions Temperature Indicating Controller CS4H / CS4L

V1.1

05/2006

- 41 -

Accuracy (Setting, indication)

Thermocouple : Within ±0.2 % of input range full scale ±1 digit or

within ±2 °C (4 °F), whichever is greater

However, R, S inputs, 0 … 200 °C (0 … 400 °F): Within ±6 °C (12 °F)

B input, 0 … 300 °C (0 … 600 °F): Accuracy is not guaranteed.

K, J, E, T, N inputs, less than 0 °C (32 °F): Within ±0.4 % of input

range full scale ±1 digit

RTD

: Within ±0.1 % of input range full scale ±1 digit or

within ±1 °C (2 °F), whichever is greater

DC Voltage and Current:

Within ±0.2 % of input range full scale ±1digit

Input sampling period

: 0.25 seconds

Control output (OUT1)

Relay contact

: Control capacity, 3 A, 250 V AC (resistive load)

1 A, 250 V AC (inductive load cos ø = 0.4)

Electrical life 100,000 times

Logic level DC 0/12 V for solid state relay:

12

+ 2

- 0

V DC maximum 40 mA (short circuit protected)

Analogue current signal : 4 … 20 mA DC

Load resistance, maximum 550

Ω

A1 output

When A1 action is set as energized, the alarm action point is set by ±deviation to the main setting
(except Process alarm).
When the input exceeds the range, the output turns ON or OFF (in the case of High/Low limit
range alarm).
When the alarm action is set as deenergized, the output acts conversely.

Setting accuracy : The same as the Indicating accuracy

Action

: ON/OFF action

Hysteresis

: Thermocouple and RTD inputs, 0.1 … 100.0 °C (°F)

DC current and DC voltage inputs, 1 … 1000

(The placement of the decimal point follows the selection)

Output

: Relay contact 1a

Control capacity 3 A, 250 V AC (resistive load)

Electrical life 100,000 times

Control action

• PID action (with auto-tuning function)

• PI action: When derivative time is set to 0

• PD action (with auto-reset function): When integral time is set to 0

• P action (with auto-reset function): When integral and derivative times are set to 0

• ON/OFF action

OUT1 proportional band (P):

Thermocouple, 0 ... 1000°C (0 ... 2000°F)

RTD, 0.0 ... 999.9°C (0.0 ... 999.9°F)

DC current and voltage, 0.0 ... 100.0%

(ON/OFF action when set to 0°C (°F), 0.0°C (°F) or 0.0%)

Integral time (I)

: 0 ... 1000 s (off when set to 0)

Derivative time (D)

: 0 ... 300 s (off when set to 0)

OUT1 proportional cycle : 1 ... 120 s (Not available for control output analogue current signal)

ARW

: 0 ... 100 %

OUT1 hysteresis

: Thermocouple and RTD inputs, 0.1 ... 100.0 °C (°F)

DC current and voltage inputs, 1 ... 1000

(The placement of the decimal point follows the selection)

SV1/SV2 external selection

: SV1 and SV2 can be selected by external contact.

Contact open between terminals 14 and 17 : SV1

Contact closed between terminals 14 and 17 : SV2

Contact

current:

6mA