Operating Instructions Temperature Indicating Controller CS4H / CS4L

V1.1

05/2006

- 25 -

Decimal point place selection [

]

• Selects the decimal point place.
• Available only for DC input
• Selection item:

(No decimal point)

(1 digit after the decimal point)

(2 digits after the decimal point)

(3 digits after the decimal point)

• Default: No decimal point
PV filter time constant setting [

]

• Sets PV filter time constant.

However, if the setting value is too large, it affects to the control result due to the delay of re-
sponse.

• Setting range: 0.0 … 10.0 seconds
• Default: 0.0 seconds
OUT1 high limit setting [

]

• Sets the high limit value for OUT1.

Not available for ON/OFF action

• Setting range: OUT1 low limit value to 100 % (Control output Relay or Logic level DC 0/12 V)

OUT1 low limit value to 105 % (Control output Analogue current

signal (4 ... 20 mA))

• Default: 100 %
OUT1 low limit setting [

]

• Sets low limit value for OUT1.

Not available for ON/OFF action

• Setting range: 0 % to OUT1 high limit value (Control output Relay or Logic level DC 0/12 V)

–5 % to OUT1 high limit value (Control output Analogue current

signal (4 ... 20 mA))

• Default: 0 %
OUT1 ON/OFF action hysteresis setting [

]

• Sets ON/OFF action hysteresis for OUT1.

Available only for ON/OFF action

• Setting range: 0.1 … 100.0 °C (°F) For DC input, 1 … 1000 (the placement of the

decimal point follows the selection)

• Default: 1.0 °C
OUT2 action mode selection [

]

• Selects OUT2 cooling action from air cooling, oil cooling and water cooling.

Not available when 2. control output (option) is not added or when OUT2 is ON/OFF action

• Selection item:

(Air cooling, linear characteristic)

(Oil cooling, 1.5th power of the linear characteristic)

(Water cooling, 2nd power of the linear characteristic)

• Default: Air cooling
OUT2 high limit setting [

]

• Sets the high limit value for OUT2.
• Not available when 2. control output (option) is not added or when OUT2 is ON/OFF action
• Setting range: OUT2 low limit value to 100 % (2. control output Relay or Logic level DC 0/12 V)

OUT2 low limit value to 105 % (2. control output Analogue current

signal (4 ... 20 mA))

• Default: 100 %
OUT2 low limit setting [

]

• Sets the low limit value for OUT2.
• Not available when 2. control output (option) is not added or when OUT2 is ON/OFF action
• Setting range: 0 % to OUT2 high limit value (2. control output Relay or Logic level DC 0/12 V)

–5 % to OUT2 high limit value (2. control output Analogue current

signal (4 ... 20 mA))

• Default: 0 %