Operating Instructions Temperature Indicating Controller CS4H / CS4L

V1.1

05/2006

- 39 -

8.3 Auto-reset (offset correction)

Auto-reset is performed to correct the offset at the point at which PV indication is stabilized within the

proportional band during the PD action.

Since the corrected value is internally memorized, it is not necessary to perform the auto-reset again as

long as the process is the same.

However, when the proportional band is set to 0, the corrected value is cleared.

(Fig. 8.3-1)

Temperature

Setting

value

Offset span

Time

Offset is corrected

Auto-reset is performed