6 Commissoning, operation

14

WIKA operating instructions digital indicator DI35-M

5.3 Storage

Permissible conditions at the place of storage:

 Storage temperature: -20 ... +80 °C
 Humidity: 0 ... 75 % relative humidity (no condensation)


Avoid exposure to the following factors:

 Direct sunlight or proximity to hot objects
 Mechanical vibration, mechanical shock (putting it down hard)
 Soot, vapour, dust and corrosive gases
 Potentially explosive environments, flammable atmospheres


Store the instrument in its original packaging in a location that fulfils the
conditions listed above. If the original packaging is not available, pack and
store the instrument as described below:

1. Wrap the instrument in an antistatic plastic film.
2. Place the instrument, along with shock-absorbent material, in the

packaging.

3. If stored for a prolonged period of time (more than 30 days), place a

bag, containing a desiccant, inside the packaging.

WARNING!
Before storing the instrument (following operation), remove
any residual media. This is of particular importance if the
medium is hazardous to health, e.g. caustic, toxic,
carcinogenic, radioactive, etc.

6 Commissoning, operation


Please read the safety instructions and installation instructions in chapter 2
before installation and keep this user manual for future reference.

6.1 Mounting

Panel cut out:

92,0

+0,8

mm x 45,0

+0,6

mm

Assembly grid: 120 mm horizontal, 96 mm vertical (recommended)