WIKA DI35 User Manual

Page 42

Advertising
background image

6 Commissoning, operation

42

WIKA operating instructions digital indicator DI35-M

PN

Function

Range of values

De-
fault

User-
level

8 = temporarily taring via

digital input

9 = fast taring on digital input
10 = fast taring on multi-

function key

11 = fast taring on digital input

or multi-function key

General settings
12

Sliding average value

0 = off
1…100 measuring values

0

2

13

Display time

0,1…10,0

1,0

2

14

Measuring time
Voltage, current
(PN0 = 1…12; 33…45)
PTxxxx 2- / 4-wire
PTxxxx 3-wire
Temperature measurement
thermocouple
Resistance 2- / 4-Leiter
Resistance 3-Leiter


0,02…10,00

0,04…10,00
0,06…10,00
0,04…10,00

0,04…10,00
0,06…10,00


1,0

1,0
1,0
1,0

1,00
1,00


2

2
2
2

2
2

15

Display mode

1 = instantaneous value
2 = MIN value
3 = MAX value
4 = HOLD value
5 = sliding average value
6 = totalizer value
7 = absolute value
8 = trigger mode

1

2

16

Activator for MIN- / MAX
value reset

0 = no reset activator
1 = digital input
2 = multi-function key
3 = digital input or multi-

function key

4 = with taring function

2

2

18

Zero point suppression

0…99999

10000

4

19

Display brightness

0…9 (0 = bright / 9 = dark)

3

8

Analogue output (Option)
20

Final value / Fullscale

-9999….99999

1000

4

21

Inital value / Offset

-9999…99999

0

4

22

Analog output

0 = de-activated
1 = instantaneous value
2 = MIN value
3 = MAX value
4 = HOLD value
5 = sliding average value
6 = totalizator value
7 = absolute value

1

4

Interface
34

Interface behaviour

0 = standard operation

0

4