6 Commissoning, operation

44

WIKA operating instructions digital indicator DI35-M

PN

Function

Range of values

De-
fault

User-
level

Setpoint 2
70

Setpoint 2 (Source / Trigger
value)

0 = not activated
1 = instantaneous value
2 = MIN value
3 = MAX value
4 = HOLD value
5 = sliding average value
6 = totalizator value
7 = absolute value

1

6

71

Threshold

-9999…99999

1000

6

72

Hysteresis

1…99999

1

6

73

Active above / below SP
value

0 = active below SP
1 = active above SP

1

6

74

Switch delay

0.0…10.0 seconds

0,0

6

75

Delay type

0 = none
1 = switch-on delay
2 = switch-off delay
3 = switch-on / -off delay
4 = suppression with activated

digital input

1

6

77

Setpoint confirmation

0 = no locking
1 = switch-off locking by multi-

function key

2 = switch-off locking by

external input

3 = switch-off locking by both
4 = no locking
5 = switch-on locking by multi-

function key

6 = switch-on locking by digital

input

7 = switch-on locking by both

0

6

Setpoint 3
80

Setpoint 3 (Source / Trigger
value)

0 = not activated
1 = instantaneous value
2 = MIN value
3 = MAX value
4 = HOLD value
5 = sliding average value
6 = totalizator value
7 = absolute value

1

6

81

Threshold

-9999…99999

1000

6

82

Hysteresis

1…99999

1

6

83

Active above / below SP
value

0 = active below SP
1 = active above SP

1

6

84

Switch delay

0.0…10.0 seconds

0,0

6