6 Commissoning, operation

40

WIKA operating instructions digital indicator DI35-M

6.7 Program number table

The program table lists all the program numbers (PN) with their function,
range of values, default values and user level.

PN

Function

Range of values

De-
fault

User-
level

0

Measuring input
Parameters 1 to 29 make use
of the factory calibration.
At PN0 = 1…12 set points
can be changed in the
measuring range.
The parameters

30 need

sensor calibration.

Current, voltage
01 = 0…20 mA
02 = 4…20 mA
03 = 0…10 V
04 = 0…5 V
05 = 0…2500 mV
06 = 0…1250 mV
07 = 0…600 mV
08 = 0…300 mV
09 = 0…150 mV
10 = 0…75 mV
11 = 0…35 mV
12 = 0…18 mV
Temperature measurement
13 = PT100 (4/2 wire)
14 = PT100 (3 wire)
15 = PT200 (4/2 wire)
16 = PT200 (3 wire)
17 = PT500 (4/2 wire)
18 = PT500 (3 wire)
19 = PT1000 (4/2 wire)
20 = PT1000 (3 wire)
21 = L
22 = J
23 = K
24 = B
25 = S
26 = N
27 = E
28 = T
29 = R
Resistance / Potentiometer

30 = ≤ 100 Ω (4/2 wire)

31 = ≤ 1 kΩ (4/2 wire)

32 = ≤ 10 kΩ (4/2 wire)
Sensor calibration

33 = 0/4…20 mA
34 = -1…10 V
35 = -1…5 V
36 = -500…2500 mV
37 = -500…1250 mV
38 = -500…600 mV
39 = ± 300 mV
40 = ± 150 mV