WIKA DI35 User Manual

Page 43

Advertising
background image

6 Commissoning, operation

WIKA operating instructions digital indicator model DI35-M

43

PN

Function

Range of values

De-
fault

User-
level

1 = transmission operation

Security settings
50

Programming lock

0000…9999

0000

8

51

Authorization code

0000…9999

0000

0

52

Userlevel

0…8

8

0

Flashing of the LED display
59

Display flashing (approx.
0.5 seconds)
No flashing
Flashing at set point 1
Flashing at set point 2
Flashing at set point 3
Flashing at set point 4
Flashing at set point 1 and 2
Flashing at set point 3 and 4
Flashing at set point 1, 2, 3
and 4



0 = no flashing
1 = flashes at 1
2 = flashes at 2
3 = flashes at 3
4 = flashes at 4
5 = flashes at 1 and 2
6 = flashes at 3 and 4
7 = flashes at 1, 2, 3 and 4

0

6

Setpoint 1
60

Setpoint 1 (Source / Trigger
value)

0 = not activated
1 = instantaneous value
2 = MIN value
3 = MAX value
4 = HOLD value
5 = sliding average value
6 = totalizer value
7 = absolute value

1

6

61

Threshold

-9999…99999

1000

6

62

Hysteresis

1…99999

1

6

63

Active above / below SP
value

0 = active below SP
1 = active above SP

1

6

64

Switch delay

0.0…10.0 seconds

0,0

6

65

Delay type

0 = none
1 = switch-on delay
2 = switch-off delay
3 = switch-on/-off delay
4 = suppression with activated

digital input

1

6

67

Setpoint confirmation

0 = no locking
1 = switch-off locking by multi-

function key

2 = switch-off locking by

external input

3 = switch-off locking by both
4 = no locking
5 = switch-on locking by multi-

function key

6 = switch-on locking by digital

input

7 = switch-on locking by both

0

6

Advertising