6 Commissoning, operation

46

WIKA operating instructions digital indicator DI35-M

PN

Function

Range of values

De-
fault

User-
level

7 = switch-on locking by both

Linearization
100

Number of additional
setpoints

0…30

0

2

101

130

Setpoints 1…30

-9999…99999

2

180

Totalizer function

0 = off
1 = Totalizer without

permanent saving (Reset
by boot-up)

2 = Totalizer with permant

saving

0

3

181

Time base of display value
for totalizator function

0 = second
1 = minute
2 = hour

0

3

182

Factor for totalizer value
(in powers of 10)

0 = 1…6 = 1.000.000

0

3

183

Decimal point for totalizer
value

00000…0,0000

0

3

184

Counter value in digit (for
Reset through 0, too), inital
value aswell

0…99999

0

3

185

Activator for counter reset
on 0
(multi-function key or digital
input: push for at least
50 ms)

0 = no reset source
1 = by multi-function key
2 = by external input
3 = by multi-function key and

digital input

4 = UP and DOWN while

showing totalisator value

0

3

186

Change display on
totalizator value

0 = no change
1 = by multi-function key
2 = by digital input

0

3

Information
200

Serial number

0…99999

0

8