SECTION 6 - JLG CONTROL SYSTEM
6-28
– JLG Lift –
3121813
Table 6-9. Calibration Ranges/Defaults
Calibration
Range
Defaults
E600
M600
BRAKE
0 to 100
25
PUMP@0%
0 to 50
6
PUMP@100%
50 to 100
100
FLOW VALVE@0%
0 to 50
44
FLOW VALVE@100%
50 to 100
60
LIFT VALVE@0%
0 to 100
40
LIFT VALVE@100%
0 to 100
70
SWING VALVE@0%
0 to 100
45
SWING VALVE@100%
0 to 100
52
TEMPERATURE
0 to 100
50
TRACTION I
0.50 to 2.00
1.00
PUMP I
0.50 to 2.00
1.00
SPEEDprop1
0 to 30
8
SPEEDprop2
0 to 30
16
SPEEDint
0.0 to 2.5
0.3
PLUGmax
30 to 100
75
TILTdelayIN*
0.0 to 5.0
1.0
TILTdelayOUT*
0.0 to 5.0
0.1
*NOTE: TiltdelayIN and TILTdelayOUT are adjusted in internal units, not in 0.1s increments.