• Installation

- Location -

Do not locate the FLR series sensor near inlets/outlets.
If there is surface wave action, then use a time-delay relay or stilling tube. If a
stilling tube is used, drill vent holes in the tube and use a spacer to assure the
float has free travel inside the tube.

Wave action may cause switch to chatter.

Use a stilling tube or time-delay
relay to prevent switch chatter.

- Mounting -

The FLR can be mounted up to 30

0

from vertical.

1. Flange Mounting
Provide the compatible mating flange on the tank and install using a suitable
gasket.

2. Plug Mounting
Provide the compatible female boss on the tank and install the FLR with a
suitable gasket, O-ring, or thread tape.

Stilling Tube

Inflow

Inflow

Spacer