5 Operation
5.4.4
Binary output 2
Parameters
Display
Setting range
1
1
The standard setting is displayed bold.
Switching function
(only with second switch-
ing output)
= Hysteresis, N/O contact
= Hysteresis, N/C contact
= Window, N/O contact
= Window, N/C contact
Chapter 6.12 "Setting the switching function
(B.Fct)", page 55
Switching point
(only with second switch-
ing output)
100 °C
Chapter 6.12 "Setting the switching function
(B.Fct)", page 55
Release point
(only with second switch-
ing output)
90 °C
Chapter 6.12 "Setting the switching function
(B.Fct)", page 55
Hysteresis
(only with second switch-
ing output and configured
switching point and
release point)
0 to 1 to 500 °C
Chapter 6.12 "Setting the switching function
(B.Fct)", page 55
Note:
Application exclusively with window switching
functions.
Switch-on delay
(only with second switch-
ing output)
0.00 to 99.99 s
Chapter 6.12 "Setting the switching function
(B.Fct)", page 55