6 Commissioning/start-up
64
6.18
Setting the display unit (D.Uni)
How to proceed:
Example:
The device scaling range was set to 0 to 150 °C.
When the device measures a temperature of 75 °C, 50 % is displayed.
Setting range:
Uni.t = Temperature unit set as for "Uni.T"
Chapter 6.4 "Setting the unit of the measured value (Uni.T)", page 44
Pro2 = Percent of the scaled measuring range = "Sc.Hi" minus "Sc.Lo"
Chapter 6.9.1 "Setting the scaling start value (Sc.Lo)", page 51
and
Chapter 6.9.2 "Setting the scaling end value (Sc.Hi)", page 52
Factory-setting:
Uni.t
Step
Activity
1
Unlock the device.
Chapter 6.2 "Unlocking the device (enter the code).", page 42
2
"Turn" until "D.Uni" appears in the bottom line.
3
"Press"
Uni.t = The measured value is displayed in the selected unit.
Chapter 6.4 "Setting the unit of the measured value (Uni.T)", page 44
or
Pro2 = The measured value is displayed in percent of the scaling range.
Chapter 6.9.1 "Setting the scaling start value (Sc.Lo)", page 51
and
Chapter 6.9.2 "Setting the scaling end value (Sc.Hi)", page 52