8 overcoming errors and malfunctions, 1 possible errors, Overcoming errors and malfunctions – JUMO 902940 DELOS T Electronic Temperature Switch with Display and Analog Output Operating Manual User Manual
Page 69: Possible errors

69
8 Overcoming errors and malfunctions
8.1
Possible errors
Display
Possible causes
Measure
•
Overrange
or underrange
•
Probe break
Check temperature and/or probe.
Device error
•
1 = Internal
communication error
•
2 = Error, analog output
•
3 = Short circuit,
switching output 1
•
4 = Short circuit,
switching output 2
•
5 = VCC 8 V outside the
working range
•
6 ... 8 = Internal
communication error
•
9 = Invalid configuration
1, 6, 7, 8: Contact the service.
2: Check ambient temperature.
Check output for cable break. Output
load too high (for current output) or
too low (for voltage output).
3, 4: Check the switching output.
5: Check voltage supply.
9: Check the configuration.
Display overrun:
Upper display: „- - - -“
Bottom display: Parameter name
Value is smaller than -9999
or exceeds +9999.
Check switching output.
Check voltage supply.